Input Type (Process)
ENTER INPUT TYPE MENU:
Press a
Press d
Press d
PROCESS SUBMENU:
Press b
Press d
Press d
Press b
Press d
Process Types: 100 mV 1 V
Display:
For 4-20 mA Input select 0-20 mA then adjust the Input/Reading accordingly.
To adjust 4-20 mA input, see example under INPUT/READING submenu. The
factory preset value is 4-20 mA.
3.2.5 Reading Configuration
is required that you put the controller in the Standby Mode for any
It
configuration change other than Set Points & Alarms.
Figure 3.4 Flow Chart for Reading Configuration Menu
1) Press a, if necessary, until CNFG prompt appears.
2) Display advances to INPT Input Menu.
3) Display flashes T.ç , RTD or PROC (Thermocouple, RTD or
Process). If the displayed input type is PROC , press a to skip to
step 6 ( PROC stops flashing).
4) Scroll through the available selection to PROC (flashing).
5) Display shows STRD stored message momentarily and then
PROC (not flashing).
6) Display flashes previous Process type selection. i.e. 0-10
(see below for Process types selection).
7) Scroll through the available Process types to the selection of
your choice.
8) Display shows STRD stored message and then advances to
RDG Reading Configuration Menu.
0-0.1
0-1.0
10 V
0 – 20 mA
0-10
0-20
21