Triac Output Unit C200H-Oa223 - Omron SYSMAC C200H Installation Manual

Programmable
Hide thumbs Also See for SYSMAC C200H:
Table of Contents

Advertisement

Specifications

Triac Output Unit C200H-OA223

Circuit Configuration
Note When the fuse blows F LED lights and bit 08 turns ON. Bits 08 through15 cannot be used as work bits.
Terminal Connections
80
Downloaded from
Elcodis.com
electronic components distributor
Max. Switching Capacity
Max. Inrush Current
Min. Switching Capacity
Leakage Current
Residual Voltage
ON Response Time
OFF Response Time
No. of Circuits
Internal Current Consumption
Fuse Rating
Power for External Supply
Weight
Dimensions
Output indicator
Internal
circuit
Fuse: 5 A 250 V (5.2-dia.x20) HT (SOC)
250 VAC max.
(1.2 A max. 4 A/Unit)
1.2 A 250 VAC, 50/60 Hz (4 A/Unit)
15 A (pulse width: 100 ms)
30 A (pulse width: 10 ms)
100 mA 10 VAC/50 mA 24 VAC/10 mA 100 VAC
min.
1.5 mA (120 VAC) max./3 mA (240 VAC) max.
1.5 VAC max. (50 to 1,200 mA)/ 5 VAC max. (10 to
50 mA)
1 ms max.
1/2 of load frequency+1 ms or less.
1 (8 points/common)
180 mA 5 VDC max.
5 A 250 V (5.2-dia.x20)
N/A
300 g max.
E-shape
OUT
L
OUT
L
Fuse
COM
250 VAC max.
Fuse blowout
detection circuit
F indicator
0
L
A0
1
A1
L
2
A2
L
3
A3
L
4
A4
L
5
A5
L
6
A6
L
7
A7
L
A8
COM
A9
NC