Transistor Output Unit C200H-Od411 - Omron SYSMAC C200H Installation Manual

Programmable
Hide thumbs Also See for SYSMAC C200H:
Table of Contents

Advertisement

Specifications

Transistor Output Unit C200H-OD411

Circuit Configuration
Note When the fuse blows F LED lights and bit 08 turns ON. Bits 08 through 15 cannot be used as work bits.
Terminal Connections
Note Be sure to supply power to A9; otherwise current will leak through the load while the output is OFF.
Downloaded from
Elcodis.com
electronic components distributor
Max. switching capacity
Min. switching capacity
Leakage Current
Residual Voltage
ON Response Time
OFF Response Time
No. of Circuits
Internal Current Consumption
Fuse Rating
Power for External Supply
Weight
Dimensions
Output LED indicator
Internal
Fuse
circuit
Fuse blowout
detection circuit
F LED
12 to 48 VDC
(1 A max., 3 A/Unit)
12 to 48 VDC 1 A (3 A/Unit)
None
0.1 mA max.
1.4 V max.
0.2 ms max.
0.3 ms max.
1 (8 points/common)
140 mA 5 VDC max.
5 A 125 V (5.2-dia.x20)
30 mA 12 to 48 VDC max.
250 g max.
A-shape
OUT
L
V
OUT
L
COM
12 to
48 VDC
0
L
A0
1
A1
L
2
A2
L
3
A3
L
4
A4
L
5
A5
L
6
A6
L
7
A7
L
A8
COM (0 V)
12 to 48 VDC
A9
Appendix B
95

Hide quick links:

Advertisement

Table of Contents
loading