I/O Connections; Terminal Block - Omron SYSMAC C200H Installation Manual

Programmable
Hide thumbs Also See for SYSMAC C200H:
Table of Contents

Advertisement

I/O Connections

4-4
I/O Connections

Terminal Block

40
Downloaded from
Elcodis.com
electronic components distributor
Connect the I/O Devices to the I/O Units using AWG 22 (cross-sectional area of
2
0.3 mm
) for 19-terminal terminal blocks and AWG 22 to 18 lead wire (cross-sec-
tional area of 0.3 to 0.75 mm
have screws with 3.5-mm diameter heads and self-raising pressure plates. Con-
nect the lead wires to the terminals as shown below. Tighten the screws with a
torque of 0.8 N S m.
If you wish to attach solderless type terminals to the ends of the lead wires, use
terminals having the dimensions shown below.
7 mm max.
The terminal block of an I/O Unit can be removed by loosening the mounting
screws. You do not have to remove the lead wires from the terminal block in or-
der to remove it from an I/O Unit.
2
) for 10 terminal terminal blocks. The terminals
7 mm max.
Locks for terminal block.
Unlock to remove the terminal
block from the I/O Unit. Make
sure the terminal block is
locked securely after wiring is
complete.