Specifications
Transistor Output Unit C200H-OD21A (Sourcing Type with Load Circuit
Protection)
Max. switching
capacity
Min. switching
capacity
Leakage Current
Residual Voltage
ON Response Time
OFF Response Time 0.3 ms max.
Circuit Configuration
Note When short-circuit/overload protection is activated, all 16 outputs will be switched OFF and the ALARM
output becomes active (low level). The problem can be detected externally by connecting a DC Input Unit to
the ALARM output or by connecting an alarm output indicator. It's not possible to connect both the Input Unit
and the indicator at the same time.
96
Downloaded from
Elcodis.com
electronic components distributor
+10%
24 VDC
/
, 1.0 A (4 A/Unit)
–15%
surge current 1.6 A (sourcing type)
PNP output
None
0.1 mA max.
0.8 V max.
0.1 ms max.
Output LED
indicator
No. of Circuits
Internal Current
Consumption
Load Short-circuit
Protection
Power for External Supply
Alarm Output (See note)
Weight
Dimensions
to
0 V
2 kΩ
Appendix B
1 (16 points/common)
160 mA, 5 VDC max.
Detection current: 1.2 A min
(1.6 A typical)
+10%
35 mA 24 VDC
/
min.
–15%
No. of outputs: 1 (2 kΩ
internal resistor)
Connectable Units: Only the
following DC Input Units and
alarm output LED indicators
can be connected:
C200H-ID001, ID211, ID212,
IM211 (DC), IM212 (DC),
ID215, ID501, MD115,
MD215, MD501
400 g max.