Inspection and Maintenance

Batteries

Downloaded from
Elcodis.com
electronic components distributor
Some RAM Packs use a battery (refer to Appendix B for specifications). When
the battery is nearly discharged, the ALARM indicator blinks and the message
"BATT FAIL" appears on the Programming Console. When this occurs, replace
the battery within one week to avoid loss of data. The battery comes together
with its connector as a set. To replace the Battery Set, follow the steps below.
The entire replacement must be completed within five minutes to ensure that the
data will not be lost.
If you are using model C200H-CPU11-E as the CPU, the battery is installed in
the Unit upon delivery.
1, 2, 3...
1. Turn OFF the power to the PC. (If the power was not already ON, turn the
power ON for at least one minute before turning the power OFF.)
2. Remove the cover from the battery compartment of the RAM Pack.
3. Remove the old Battery Set.
4. Install the new Battery Set as shown shown in the following diagram.
Battery
connector
Battery Set
5. Replace the cover of the battery compartment.
6. Press CLR, FUN, MONTR, MONTR or just turn the power to the PC OFF
and then ON again to clear the error message on the Programming Con-
sole.