Specifications
Contact Output Unit C200H-OC221
Circuit Configuration
Terminal Connections
82
Downloaded from
Elcodis.com
electronic components distributor
Max. switching capacity
Min. switching capacity
Relay
Service Life of Relay
ON Response Time
OFF Response Time
No. of Circuits
Internal Current Consumption
Weight
Dimensions
Output LED indicator
Internal
circuit
250 VAC 24 VDC max.
(inductive load: 2 A resistive load: 2 A) (8 A/Unit)
2 A 250 VAC (cos of phase angle = 1), 2 A
250 VAC (cos of phase angle = 0.4), 2 A 24 VDC
8 A/Unit
10 mA 5 VDC
G6B-1174P-FD-US (24 VDC) w/socket
Electrical: 500,000 operations (resistive load)/
100,000 operations (inductive load)
Mechanical: 50,000,000 operations
10 ms max.
10 ms max.
1 (8 points/common)
10 mA 5 VDC max. 75 mA 25 VDC (8 points ON
simultaneously.)
250 g max.
A-shape
OUT
L
OUT
L
COM
250 VAC 24 VDC max.
0
L
A0
1
A1
L
2
A2
L
3
A3
L
4
A4
L
5
A5
L
6
A6
L
7
A7
L
COM
A8
A9
NC
Appendix B