I/O Connections
AC Input Units
Output Units
Downloaded from
Elcodis.com
electronic components distributor
Contact output
AC Switching
Prox.
switch
main
circuit
Caution
When using Reed switch as the input contacts for AC Input Units, be sure the
!
allowable current of the switch is at least 1 A. Using switches with lower capaci-
ties may cause the contacts to fuse due to surge current.
A fuse placed in the output circuit will protect the output element, circuit board,
etc., in the event of a short circuit in the output circuit. Although some transistor
Output Units and Triac Output Units have a built-in fuse, it is recommended that
you connect an external fuse to each Output Unit for extra safety and ease of
maintenance.
Section
4-4
IN
AC input
COM
IN
AC input
COM
43