Programming Instructions
Name
Mnemonic
SUBROUTINE START
SBN(92)
RETURN
RET(93)
WATCHDOG TIMER
REFRESH
(@)WDT(94)
I/O REFRESH
(@)IORF(97)
Data Areas
These footnote tables show the actual ranges of all data areas. Bit numbers are provided (except for DM and TC areas); remove the rightmost two digits for word numbers.
IR
00000 to 23515 23600 to 25507
Downloaded from
Elcodis.com
electronic components distributor
Symbol
SBN(92)
RET(93)
WDT(94) T
IORF(97)
St
E
SR
HR
TR
HR 0000 to 9915
TR 0 to 7
Function
Marks the start of subroutine N.
N
Marks the end of a subroutine and returns
control to the main program.
Sets the maximum and minimum limits for
the watchdog timer (normally 0 to 130 ms).
New limits:
Maximum time = 130 + (100 x T)
Minimum time = 130 + (100 x (T–1))
Refreshes all I/O words between the start
(St) and end (E) words. Only I/O words
may be designated. Normally these words
are refreshed only once per cycle, but re-
freshing words before use in an instruction
can increase execution speed. St must be
less than or equal to E.
AR
LR
AR 0000 to 2715
LR 0000 to 6315
TC 000 to 511
Appendix E
Operand Data Areas
N:
00 to 99
None
T:
0 to 63
St/E:
IR
TC
DM
Read/Wr: DM 0000 to DM 0999
Rd only: DM 1000 to DM 1999
#
0000 to 9999
or 0000 to FFFF