Ac Input Units - Omron CQM1 Operation Manual

Programmable controllers
Hide thumbs Also See for CQM1:
Table of Contents

Advertisement

Unit Specifications

2-6-9 AC Input Units

Item
Input Voltage
100 to 120 VAC
Input
20 kΩ (50 Hz), 17 kΩ (60 Hz)
Impedance
Input Current
5 mA typical (at 100 VAC)
ON Voltage
60 VAC min.
OFF Voltage
20 VAC max.
ON Delay
35 ms max.
OFF Delay
55 ms max.
No. of Inputs
8 points (8 points/common, 1 circuit)
Internal Current
50 mA max. at 5 VDC
Consumption
Weight
210 grams max.
Circuit
Configuration
COM
Terminal
Connections
58
CQM1-IA121
+10%
/
, 50/60 Hz
--15%,
IN
470 Ω
68 kΩ
IN
0.15 µF
2.7 kΩ
0
B0
1
A0
2
B1
3
A1
4
B2
5
A2
6
B3
7
A3
NC
B4
NC
A4
NC
B5
NC
A5
NC
B6
NC
A6
NC
B7
NC
A7
COM
B8
COM
A8
100 to 120 VAC
200 to 240 VAC
38 kΩ (50 Hz), 32 kΩ (60 Hz)
6 mA typical (at 200 VAC)
150 VAC min.
40 VAC max.
35 ms max.
55 ms max.
8 points (8 points/common, 1 circuit)
50 mA max. at 5 VDC
210 grams max.
IN
Input
LED
820 Ω
IN
Internal
Circuits
COM
0.082 µF
200 to 240 VAC
Section 2-6
CQM1-IA221
+10%
/
, 50/60 Hz
--15%,
Input
LED
220 kΩ
Internal
Circuits
8.2 kΩ
0
B0
1
A0
2
B1
3
A1
4
B2
5
A2
6
B3
7
A3
NC
B4
NC
A4
NC
B5
NC
A5
NC
B6
NC
A6
NC
B7
NC
A7
COM
B8
COM
A8

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sysmac cqm1

Table of Contents