Appendix A: Programming Sheets; A.1: Digital Communicator Options Program Sheets - Fire-Lite 411UD Manual

Digital alarm communicator/transmitters
Hide thumbs Also See for 411UD:
Table of Contents

Advertisement

Appendix A: Programming Sheets

A.1 Digital Communicator Options Program Sheets
--To enter Programming Mode, press the MODE key, 7764 and then the [ENTER/STORE] key.
00
01
02
03
Addresses 00 to 19 store the Primary Central Station phone number. Enter 'F' to represent the end of number.
Primary Central Station Communication Format: Valid entries are 0 to 9 and A to E.
20
Primary Central Station Account Code: Valid entries are 0 to 9 and A to F.
21
22
23
24
Primary Central Station 24-hour Test Time: Use military time (i.e. 1400 for 2:00 PM).
25
26
27
28
Primary Number Test Time Interval. Enter '0' for 24-hour; '1' for 12-hour; '2' for 8-hour; '3' for 6-hour.
29
30
31
32
33
Addresses 30 to 49 store the Secondary Central Station phone number. Enter 'F' to represent the end of number.
Secondary Central Station Communication Format: Valid entries are 0 to 9 and A to E.
50
Secondary Central Station Account Code: Valid entries are 0 to 9 and A to F.
51
52
53
54
Secondary Central Station 24-hour Test Time: Use military time (i.e. 1400 for 2:00 PM).
55
56
57
58
Secondary Number Test Time Interval. Enter '0' for 24-hour; '1' for 12-hour; '2' for 8-hour; '3' for 6-hour.
59
AC Loss Reporting Delay. Enter '0' for no delay; '1' for 1 hours; '2' for 2 hours; '3' for 6 hours; '4' for 7 hours;
60
'5' for 8 hours; '6' for 9 hours; '7' for 10 hours; '8' for 11 hours; '9' for 12 hours; 'A' for 13 hours; 'B' for 14 hours; 'C' for
15 hours; 'D' for 16 hours; 'E' for 17 hours; 'F' for 18 hours.
Backup Reporting. Enter '0' to report to Secondary phone number as backup only; '1' to report to both Primary
61
and Secondary phone number for all reports/messages; '2' reports go to first available receiver.
Reserved for Future Use.
62
Reserved for Future Use.
63
Communicator Enable/Disable. Enter '0' to disable communication to Central Station; '1' to enable. Default
64
entry of '0' causes the 411/411UD to annunciate a DACT trouble immediately on power-up.
Input Channel 1 Function Selection. Enter '0' for fire alarm; '1' for host control panel trouble; '2' for fire super-
65
visory; '4' for AC loss.
Input Channel 2 Function Selection. Enter '0' for fire alarm; '1' for host control panel trouble; '2' for fire super-
66
visory; '4' for AC loss.
Input Channel 3 Function Selection. Enter '0' for fire alarm; '1' for host control panel trouble; '2' for fire super-
67
visory; '4' for AC loss.
Input Channel 4 Function Selection. Enter '0' for fire alarm; '1' for host control panel trouble; '2' for fire super-
68
visory; '4' for AC loss - 411UD Only
411 & 411UD Manual — P/N LS10105-000GE-E:A 1/29/2014
04
05
06
07
08
34
35
36
37
38
09
10
11
12
13
39
40
41
42
43
14
15
16
17
18
44
45
46
47
48
19
49
51