Programming Reference Sheets
Appendix C
...To enter Programming Mode, press the MODE key, the code 7764 and then the [ENTER/STORE] key...
❐
❐
❐
❐
❐
00
01
02
03
Addresses 00 to 15 store the Primary Phone Number. Enter 'F' to represent the end of the number. Default all Fs
❐
Primary Communication Format: Enter 0 - F.
16
❐
❐
❐
❐
Primary Account Code: Valid entries are '0 - F'. Default is '0000'.
17
18
19
20
❐
❐
❐
❐
Primary 24-Hour Test Time. Enter military time (i.e. 1400 for 2 PM).
21
22
23
24
❐
Primary Number Test Time Interval. Enter default '0' for 24 hr.; '1' for 12 hr.
25
❐
❐
❐
❐
❐
26
27
28
29
Addresses 26 to 41 store the Secondary Phone Number. Enter 'F' to represent the end of the number. Default all Fs
❐
Secondary Communication Format: Enter 0 - F.
42
❐
❐
❐
❐
Secondary Account Code: Valid entries are '0 - F'.
43
44
45
46
❐
❐
❐
❐
Secondary 24-Hour Test Time. Enter military time (i.e. 1400 for 2 PM).
47
48
49
50
❐
Secondary Number Test Time Interval. Enter default '0' for 24 hr.; '1' for 12 hr.
51
❐
❐
Start Monitoring Address.
52
53
❐
❐
End Monitoring Address.
54
55
❐
UDACT-F Communication Selection. Enter '0' to disable UDACT-F communication; '1' for zone reporting
56
receive only communication; '2' for zone reporting receive/transmit communication; '3' for point reporting receive
only communication; '4' for point reporting receive/transmit communication; '5' for code wheel matching reporting,
receive only; '6' for code wheel matching point reporting, receive/transmit.
❐
Backup Reporting. Enter '0' to have secondary phone number act as backup only; '1' to have secondary phone
57
number receive all reports and messages along with primary phone number.
❐
Touchtone/Rotary Select. Enter '0' for touchtone dialing; '1' for rotary dialing.
58
❐
Make/Break Ratio. If rotary dialing is selected in Address 58; enter '0' for a 67/73 make/break ratio; '1' for a
59
62/38 make/break ratio.
❐
Leave default of '0'.
60
❐
Leave default of '0'
61
❐
AC Loss Delay. Enter '0' for no time delay after AC loss; '1' for 6 hours; '2' for 7 hours; '3' for 8 hours; '4' for
62
9 hours; '5' for 10 hours; '6' for 11 hours; '7' for 15 hours; '8' for 16 hours; '9' for 17 hours; 'A' for 18 hours; 'B' for
19 hours; 'C' for 20 hours; 'D' for 21 hours; 'E' for 22 hours; 'F' for 23 hours. Default is '0'.
❐
Host Panel ID. Enter '0' for MS-9200; '2' for Sensiscan 2000; '5' for MS-9600; all other entries are invalid.
63
❐
❐
Loop Number for General Reports. Factory set to '00'.
64
65
❐
❐
❐
Sensor Number for General Reports. Factory set to '000'.
66
67
68
52
Programming Reference Sheets
❐
❐
❐
❐
04
05
06
07
❐
❐
❐
❐
30
31
32
33
Document #50049
❐
❐
❐
❐
08
09
10
11
12
❐
❐
❐
❐
34
35
36
37
38
Rev.E0
1/22/01
P/N 50049:E0
❐
❐
❐
13
14
15
❐
❐
❐
39
40
41