Fire-Lite 411UD Manual page 52

Digital alarm communicator/transmitters
Hide thumbs Also See for 411UD:
Table of Contents

Advertisement

Programming Sheets
Future Use
69
70
71
Future Use
72
73
74
Future Use
75
76
77
Future Use
78
79
80
Touchtone/Rotary Select for Primary Phone. Enter '0' for touchtone dialing; '1' for rotary dialing.
81
Make/Break Ratio for Primary Phone. Enter '0' for 67/33 ratio; '1' for 62/38 ratio.
82
Touchtone/Rotary Select for Secondary Phone. Enter '0' for touchtone dialing; '1' for rotary dialing.
83
Make/Break Ratio for Secondary Phone. Enter '0' for 67/33 ratio; '1' for 62/38 ratio.
84
Future Use.
85
Future Use.
86
Output Relay Enable. Enter '0' to disable relay; '1' to enable relay.
87
Output Relay Function Selection. Enter '0' for activation on fire alarm; '1' for host control panel trouble; '2' for
88
fire supervisory; '4' for AC loss; '6' for communication failure; '7' for DACT trouble.
Trouble Call Limit. Enter a '0' to disable this feature; '1' to enable Trouble Call Limit. Factory default is '0' for
89
disabled.
Panel Unlock. Enter '0' for password unlock, '1' for permanent unlock.
90
Future Use.
91
92
93
94
95
96
97
Addresses 94 to 113 store the Service Terminal 1 Phone Number. Valid entries are 0 - 9 and A - E. 'F'
112
113
designates the end of the phone number. - 411UD Only
Ring Count on Primary Phone Line. Enter number of rings prior to panel answering call. Valid entries
114
115
are 00 to 25 (00 = no answer). Factory default is 03. - 411UD Only
Future Use.
116
117
118
119
120
Addresses 117 to 136 store the Service Terminal 2 Phone Number. Valid entries are 0-9 and
134
135
136
A-E. 'F' designates the end of the phone number. - 411UD Only
Upload/Download Backup Reporting. Enter '0' for Upload/Download reports to go to the Secondary Central
137
Station Phone Number on backup only; '1' for Upload/Download reports to always go to the Secondary; '2' for
Upload/Download reports to go to the first available Central Station phone number - 411UD Only.
52
98
99
100
101
102
121
122
123
124
Digital Communicator Options Program Sheets
103
104
105
106
125
126
127
128
411 & 411UD Manual — P/N LS10105-000GE-E:A 1/29/2014
107
108
109
110
129
130
131
132
133
111

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

411