Program Mode

3.4 Program Mode
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION
This product incorporates field-programmable software. In order for the product to comply with the requirements in the Standard
for Control Units and Accessories for Fire Alarm Systems, UL 864, certain programming features or options must be limited to
Program feature or
Permitted in UL
option
864? (Y/N)
AC Loss Delay
Trouble Call Limit
All programming selections made during Program Mode are stored in nonvolatile Electrically-
Erasable Programmable Read-Only Memory (EEPROM). This ensures that the 411/411UD will
retain all entries made in Programming Mode even if power is removed.
The user must program the primary and secondary phone numbers, account numbers, 24-hour test
report times and verify event codes for each Central Station account. The 411/411UD is shipped
with the program options/features already factory programmed. Alternative options/features may
be programmed if desired. If all factory default settings are acceptable, programming is complete.
Program Mode is entered by pressing the MODE key followed by the 4-digit program mode entry
code 7764 and pressing the [ENTER/STORE] key. Accessing this mode requires authentication.
Refer to Section 3.2.
• 7764 spells PROG on a Touch-Tone
If an incorrect key is entered, reenter the proper 4-digit code before pressing the [ENTER/STORE]
key. Note that as information is entered into the 411/411UD, the digits will scroll across the Pro-
grammer display from right to left.
A pause of up to 10 seconds between each number is allowed while entering the code. After press-
ing the [ENTER/STORE] key, the digital communicator will be in Program Mode. A maximum
of 10 minutes idle time is allowed at this point before beginning program entries and between each
key stroke, otherwise, the digital communicator will return to Normal Mode. All entries made prior
to the 10 minute time-out are valid and are stored.
411 & 411UD Manual — P/N LS10105-000GE-E:A 1/29/2014
AND OTHER INVOLVED PARTIES
specific values or not used at all as indicated below:
AC Loss Delay = 0, 1, 2 (factory default), 6, 7, 8, 10, 11, 12,
Y
13, 14, 15, 16, 17, or 18 hours
Refer to "AC Loss Reporting Delay (60)" on page 36.
Program Address 89 = 0 (factory default): unlimited
calling to Central Station for any trouble condition
N
Program Address 89 = 1: limits call for each unique
trouble to 10 within a 24 hour period
___7
__77
_776
7764
Possible settings
®
phone.
Modes of Operation
Settings permitted in
UL 864
AC Loss Delay =
1 or 2 hours
Program Address 89 =
0 for unlimited Central
Station
trouble calls
27