Ademco Contact ID Format Event Code Description
Ademco Contact ID Reporting Structure
A typical printout from a Central Station receiver (such as the Ademco 685) of alarm and trouble
reports in the Ademco Contact ID Reporting Structure follows:
Time
Date
11:28
03/25
11:28
03/25
11:28
03/25
11:28
03/25
11:28
03/25
11:28
03/25
11:28
03/25
11:28
03/25
411 & 411UD Manual — P/N LS10105-000GE-E:A 1/29/2014
Rcvr/Line ID
SSSS
QXYZ
11
7777
E110
11
7777
E111
11
7777
E380
11
7777
R110
11
7777
R111
11
7777
R380
11
7777
E158
11
7777
E151
Central Station Communications
GG
CCCC
00
C001 - general fire alarm on Channel/Input 1
00
C002 - smoke detector alarm on Channel/Input 2
00
C003 - fault on Channel/Input 3
00
C001 - Channel/Input 1 alarm restored
00
C002 - smoke detector Channel/Input 2 restored
00
C003 - Channel/Input 3 fault restored
00
C004 - high temperature, Channel/Input 4 - 411UD
Only
00
C004 - gas detected, Channel/Input 4 - 411UD
Only
45