A.2: Digital Communicator Options Program Sheet (Factory Defaults) - Fire-Lite 411UD Manual

Digital alarm communicator/transmitters
Hide thumbs Also See for 411UD:
Table of Contents

Advertisement

Digital Communicator Options Program Sheet (Factory Defaults)
A.2 Digital Communicator Options Program Sheet (Factory
Defaults)
--To enter Programming Mode, press the MODE key, 7764 and then the [ENTER/STORE] key.
F
F
F
F
F
00
01
02
03
Addresses 00 to 19 store the Primary Central Station phone number. Enter 'F' to represent the end of number.
E
Primary Central Station Communication Format: 'E' for Ademco Contact ID Format.
20
0
0
0
0
Primary Central Station Account Code.
21
22
23
24
0
0
0
0
Primary Central Station 24-hour Test Time. '0000' = 12:00 midnight.
25
26
27
28
0
Primary Number Test Time Interval. '0' for 24 hours.
29
F
F
F
F
F
30
31
32
33
Addresses 30 to 49 store the Secondary Central Station phone number. Enter 'F' to represent the end of number.
E
Secondary Central Station Communication Format. 'E' for Ademco Contact ID Format.
50
0
0
0
0
Secondary Central Station Account Code.
51
52
53
54
0
0
0
0
Secondary Central Station 24-hour Test Time: '0000' = 12:00 midnight.
55
56
57
58
0
Secondary Number Test Time Interval. '0' for 24 hours.
59
2
AC Loss Reporting Delay. '2' for 2 hour delay.
60
0
Backup Reporting. '0' to report to Secondary Central Station phone number as backup only.
61
1
Future Use.
62
0
Future Use.
63
0
Communicator Enable/Disable. '0' disables communication to Central Station.
64
0
Input Channel 1 Function Selection. '0' for fire alarm.
65
1
Input Channel 2 Function Selection. '1' for host control panel trouble.
66
2
Input Channel 3 Function Selection. '2' for fire supervisory.
67
4
Input Channel 4 Function Selection. '4' for AC loss - 411UD Only.
68
0
0
0
Future Use
69
70
71
0
0
0
Future Use
72
73
74
0
0
0
Future Use
75
76
77
0
0
0
Future Use
78
79
80
0
Touchtone/Rotary Select for Primary Phone. '0' for touchtone dialing.
81
0
Make/Break Ratio for Primary Phone. '0' for 67/33 ratio.
82
411 & 411UD Manual — P/N LS10105-000GE-E:A 1/29/2014
F
F
F
F
F
04
05
06
07
08
F
F
F
F
F
34
35
36
37
38
F
F
F
F
F
09
10
11
12
13
F
F
F
F
F
39
40
41
42
43
Programming Sheets
F
F
F
F
F
14
15
16
17
18
F
F
F
F
F
44
45
46
47
48
19
49
53

Hide quick links: