Modes of Operation

Ademco Contact ID Format Primary Central Station Event Codes

If 'E' is entered for address 20, the following data is automatically programmed for the Primary
Central Station phone number event codes. Enter '000' for the Setting to disable the report to the
Central Station. The Channel # is not programmable.
Address
138 - 140
141 - 143
144 - 146
147 - 149
150 - 152
153 - 155
156 - 158
159 - 161
162 - 164
165 - 167
168 - 170
171 - 173
174 - 176
177 - 179
180 - 182
183 - 185
186 - 188
189 - 191
192 - 194
4+2 Standard and 4+2 Express Formats Primary Central Station Event Codes
If 1, A, or C is entered for address 20, the following data is automatically programmed for the Pri-
mary Central Station phone number event codes. Enter '00' for the Setting to disable the report to
the Central Station.
Address
138 - 139
140 - 141
142 - 143
144 - 145
146 - 147
148 - 149
150 - 151
152 - 153
154 - 155
156 - 157
158 - 159
160 - 161
162 - 163
164 - 165
166 - 167
168 - 169
170 - 171
172 - 173
174 - 175
176 - 177
178 - 179
Table 3.2 4+2 Standard and 4+2 Express Formats - Primary
30
Description
Primary # Input Channel 1 Active Event Code
Primary # Input Channel 2 Active Event Code
Primary # Input Channel 3 Active Event Code
Primary # Input Channel 4 Active Event Code - 411UD Only
Primary # Input Channel 1 Fault Event Code
Primary # Input Channel 2 Fault Event Code
Primary # Input Channel 3 Fault Event Code
Primary # Input Channel 4 Fault Event Code - 411UD Only
Primary # Phone Line 1 Voltage Fault Event Code
Primary # Phone Line 2 Voltage Fault Event Code
Primary # Phone Number 1 Comm. Fault Event Code
Primary # Phone Number 2 Comm. Fault Event Code
Primary # System Off Normal Fault Code
Primary # System Test Message
Primary # System Abnormal Test Message
Primary # Upload/Download Request Code - 411UD Only
Primary # Upload Successful Code - 411UD Only
Primary # Download Successful Code - 411UD Only
Primary # Upload/Download Failed Code - 411UD Only
Table 3.1 Ademco Contact ID Format - Primary
Description
Primary # Input Channel 1 Active Event Code
Primary # Input Channel 2 Active Event Code
Primary # Input Channel 3 Active Event Code
Primary # Input Channel 4 Active Event Code - 411UD Only
Primary # Input Channel 1 Fault Event Code
Primary # Input Channel 2 Fault Event Code
Primary # Input Channel 3 Fault Event Code
Primary # Input Channel 4 Fault Event Code - 411UD Only
Primary # Phone Line 1 Voltage Fault Event Code
Primary # Phone Line 2 Voltage Fault Event Code
Primary # Phone Number 1 Comm. Fault Event Code
Primary # Phone Number 2 Comm. Fault Event Code
Primary # System Off Normal Fault Code
Primary # Input Channel 1 Active Restoral Code
Primary # Input Channel 2 Active Restoral Code
Primary # Input Channel 3 Active Restoral Code
Primary # Input Channel 4 Active Restoral Code - 411UD Only
Primary # Input Channel 1 Fault Restoral Code
Primary # Input Channel 2 Fault Restoral Code
Primary # Input Channel 3 Fault Restoral Code
Primary # Input Channel 4 Fault Restoral Code - 411UD Only
Setting
411 & 411UD Manual — P/N LS10105-000GE-E:A 1/29/2014
Program Mode
Channel/Input #
110
001
373
002
200
003
301
004
380
001
380
002
380
003
380
004
351
000
352
000
354
001
354
002
308
000
602
000
608
000
411
000
416
000
412
000
413
000
Setting
11
FF
83
92
F1
F2
F3
F4
64
65
6A
6B
6F
E1
E2
E3
93
D1
D2
D3
D4