Programming Sheets

Appendix A
A.1 Digital Communicator Options Program Sheets
--To enter Programming Mode, press the MODE key, 7764 and then the [ENTER/STORE] key.
00
01
02
03
04
Addresses 00 to 19 store the Primary Central Station phone number. Enter 'F' to represent the end of number.
Primary Central Station Communication Format: Valid entries are 0 to 9 and A to F.
20
21
22
23
24
25
26
27
28
Primary Number Test Time Interval. Enter '0' for 24-hour; '1' for 12-hour; '2' for 8-hour; '3' for 6-hour.
29
30
31
32
33
34
Addresses 30 to 49 store the Secondary Central Station phone number. Enter 'F' to represent the end of number.
Secondary Central Station Communication Format: Valid entries are 0 to 9 and A to F.
50
51
52
53
54
55
56
57
58
Secondary Number Test Time Interval. Enter '0' for 24-hour; '1' for 12-hour; '2' for 8-hour; '3' for 6-hour.
59
AC Loss Reporting Delay. Enter '0' for no delay; '1' for 1 hours; '2' for 2 hours; '3' for 6 hours; '4' for 7 hours;
60
'5' for 8 hours; '6' for 9 hours; '7' for 10 hours; '8' for 11 hours; '9' for 12 hours; 'A' for 13 hours; 'B' for 14 hours; 'C' for
15 hours; 'D' for 16 hours; 'E' for 17 hours; 'F' for 18 hours.
Backup Reporting. Enter '0' to report to Secondary phone number as backup only; '1' to report to both Primary
61
and Secondary phone number for all reports/messages; '2' reports go to first available receiver.
Reserved for Future Use.
62
DACT Trouble Reminder. Enter '0' to disable; '1' to enable.
63
Operational Mode Selection. Enter '0' for stand-alone/communicator disabled; '1' for stand-alone/communica-
64
tor enabled; '2' for slave/communicator enabled; '3' for slave/communicator disabled. Default setting is '0'.
Input Channel 1 Function Selection. Enter '0' for fire alarm; '1' for pull station; '2' for normally open contact;
65
'3' for host panel trouble; '4' for supervisory; '5' for supervisory autoresettable; '6' for waterflow silenceable; '7' for
waterflow nonsilenceable.
Input Channel 2 Function Selection. Enter '1' for pull station; '2' for normally open contact; '3' for host panel
66
trouble; '4' for supervisory; '5' for supervisory autoresettable; '6' for waterflow silenceable; '7' for waterflow nonsi-
lenceable.
Input Channel 3 Function Selection. Enter '0' for fire alarm; '1' for pull station; '2' for normally open contact;
67
'3' for host panel trouble; '4' for supervisory; '5' for supervisory autoresettable; '6' for waterflow silenceable; '7' for
waterflow nonsilenceable.
Input Channel 4 Function Selection. Enter '1' for pull station; '2' for normally open contact; '3' for host panel
68
trouble; '4' for supervisory; '5' for supervisory autoresettable; '6' for waterflow silenceable; '7' for waterflow nonsi-
lenceable.
Input Channel 1 Delay Timer. Enter 0 - 179 seconds delay. Factory default is '000' for no delay.
69
70
71
Does not delay Input Channels programmed for fire functions.
Input Channel 2 Delay Timer. Enter 0 - 179 seconds delay. Factory default is '000' for no delay.
72
73
74
Does not delay Input Channels programmed for fire functions.
Programming Sheets
05
06
07
08
09
Primary Central Station Account Code: Valid entries are 0 to 9 and A to F.
Primary Central Station 24-hour Test Time: Use military time (i.e. 1400 for 2:00 PM).
35
36
37
38
39
Secondary Central Station Account Code: Valid entries are 0 to 9 and A to F.
Secondary Central Station 24-hour Test Time: Use military time (i.e. 1400 for 2:00 PM).
411UDAC
Document #51073
10
11
12
13
14
40
41
42
43
44
Rev. D 12/09/2008
P/N 51073:D
15
16
17
18
19
45
46
47
48
49
67