Installation

2.6 Optional Programmer

The optional Fire-Watch 411 Series DACT Programmer (Model PRO-411) is used to:
switch between the digital communicator's five Modes of operation
set the digital communicator's 24 hour internal clock in Real-Time Clock Mode
program the 411/411UD digital communicator in Program Mode
test the telephone lines interconnect in Troubleshoot Mode
return all digital communicator programming to the factory default settings in Default Mode
To use the PRO-411 Programmer:
1.
Remove all power from the 411/411UD.
2.
Remove the two screws holding the 411/411UD cover in place and remove the cover.
3.
Connect the Programmer cable to connector J2 located in the upper right corner of the
411/411UD. Note that the key on the connector must align with the slot in the J2 connector.
4.
Reapply power to the 411/411UD.
5.
Operate the Programmer by pressing the MODE key. Enter the appropriate four digit code
and then press the [ENTER/STORE] key.
Note that it is not possible to switch from Normal Mode to any other mode if any of the 3 (411) or
4 (411UD) Channels is programmed for fire alarm or fire supervisory, and is active, that is, in alarm
(shorted).
Cable attached to Programmer
411/411UD
20
Programmer
J2 connector
Figure 2.5 Programmer Connection to 411/411UD
411 & 411UD Manual — P/N LS10105-000GE-E:A 1/29/2014
Optional Programmer