Program Mode

Primary Central Station Number Communication Format (20)

One location is needed to select the Communication Format to the primary phone number. Address
20 is used for this purpose. The factory default setting for this address is 'E', which is Contact ID
Format. You may enter '0' through 'D' in place of the default, then press [ENTER/STORE].
Choose from the list of formats below:
Consult the Central Station for proper Format selection. For any Format chosen, all event codes
are automatically programmed by the 411/411UD. Refer to Tables 3.1, 3.2, and 3.3.
Event Codes - Setting Entries
The Format selected in address 20 will cause the digital communicator to automatically program
addresses 138 - 201 with the factory default settings. Any of the Event Code settings may be
altered. Consult your Central Station prior to altering the event code settings. An entry of all zeros
for any event code will cause the communicator to NOT transmit the report. Transmission of
reports to either or both Central Station phone numbers may be disabled.
Upon accessing the first address (address 138) shown in Table 3.2, the following may be displayed
on the Programmer 7-Segment Display, if the corresponding Format was selected in address 20.
The first three locations on the left of the Programmer display represent the memory address 138 of
the Format previously selected in address 20. The last location 1 (farthest right) represents the con-
tents of memory address 138 (which is the first digit of the event code).
The following Tables list the data which is automatically programmed for each Format that can be
selected in address 20. The addresses shown in each Table contain the Setting data which is auto-
matically programmed by the 411/411UD. To change the value, key in the new digit and then press
the [ENTER/STORE] key to save the new value. Use the Up and Down Arrow keys to increment
to the next address or decrement to the previous address.
411 & 411UD Manual — P/N LS10105-000GE-E:A 1/29/2014
0: 4+1 Ademco Express Standard, DTMF, 1400/2300 ACK
1: 4+2 Ademco Express Standard, DTMF, 1400/2300 ACK
2: 3+1 Standard 1800 Hz Carrier, 2300 Hz ACK
3: 3+1 Expanded 1800 Hz Carrier, 2300 Hz ACK
4: 3+1 Standard 1900 Hz Carrier, 1400 Hz ACK
5: 3+1 Expanded 1900 Hz Carrier, 1400 Hz ACK
6: 4+1 Standard 1800 Hz Carrier, 2300 Hz ACK
7: 4+1 Expanded 1800 Hz Carrier, 2300 Hz ACK
8: 4+1 Standard 1900 Hz Carrier, 1400 Hz ACK
9: 4+1 Expanded 1900 Hz Carrier, 1400 Hz ACK
A: 4+2 Standard 1800 Hz Carrier, 2300 Hz ACK
B: 4+2 Expanded 1800 Hz Carrier, 2300 Hz ACK
C: 4+2 Standard 1900 Hz Carrier, 1400 Hz ACK
D: 4+2 Expanded 1900 Hz Carrier, 1400 Hz ACK
E: Contact ID, DTMF, 1400/2300 ACK
F: Future use