Fig. 7.12
• Press buttons
the "PM15" program that enables the ex-
ternal probe (Fig. 7.13)
Fig. 7.13
• Modify the programmed SET by acting
on buttons
or
60 is displayed, wait for the number pro-
grammed to flash (Fig. 7.14)
Fig. 7.14
• To exit programming, press button .
COMMISSIONING
or
to display
until a setting of
7.10 Setting the K coefficient of the
external temperature probe
The boiler is set with a K coefficient equal to
zero for boiler functioning without the probe
connected.
If the boiler is NOT EQUIPPED with the re-
mote control (optional) refer to Fig. 7.15.
C.h. flow temperature °C
K=6
K=4 K=3
80
70
60
50
40
30
20
20
15
10
5
0
External temperature °C
Fig. 7.15
If the boiler is EQUIPED with the remote
control (optional) refer to Fig. 7.16.
In this case K setting must be done from the
remote control.
C.h. flow temperature °C
K=6
K=4
K=3
80
70
60
50
40
30
20
20
15
10
5
0
External temperature °C
Fig. 7.16
The K coefficients is a parameter that in-
creases or reduces the boiler flow tempera-
ture when the outside temperature changes.
When installing the external probe it is nec-
K=2
K=1,5
K=1
K=0,5
-5
-10
-15
-20
-25
K=2
K=1,5
K=1
K=0,5
-5
-10
-15
-20
-25
- 57 -