Selection Aid For Possible Equipment Levels With Components Of The Logamatic Ems Control System - Buderus Logamax plus GB162 Technical Manual

Gas condensing boiler output range from 2.7 kw to 100 kw
Hide thumbs Also See for Logamax plus GB162:
Table of Contents

Advertisement

4
Heating control
4.6
Selection aid for possible equipment 'levels with components of the Logamatic
EMS control system
Control components and their functions
Boiler components
Universal burner control unit UBA3.5
Logamatic BC10 base controller
RC25 programming unit
As room temperature-dependent control
As a remote control in conjunction with the RC35
1)
programming unit
RC35 programming unit
As weather-compensated control
As room temperature-dependent control
Connection of an external room temperature sensor
2)
As remote control
Cylinder connection set AS-E
Function modules
4)
WM10
low loss header module
6)
MM10 mixer module
7)
SM10 solar module
Logamatic Easycom telecontrol modem
Control system extension options
Solar controller for second consumer (central heating
backup) can be integrated
External interlocking (floating contact)
External heat demand (floating contact)
External heat demand 0-10 V (EM10 fault message module)
Central fault message (EM10 fault message module)
Remote monitoring
Remote configuration
Second solenoid valve, e.g. for LPG (VM10 control module)
Table 15 Selection aid for the possible equipment 'levels of the Logamax plus GB162 with components of the
Logamatic EMS control system
1) As a remote control for heating circuit 1, if the RC35 programming unit is installed inside the appliance or as a remote control for heating
circuit 2.
2) Only one RC35 programming unit per system: If the RC35 programming unit is installed in the appliance or a second heating circuit is
planned, then an additional RC25 programming unit per heating circuit as a remote control is required.
3) AS-E includes DHW temperature sensors for DHW heating with plug and dummy segments.
4) Factory-connected integral DHW cylinder
5) Up to two modules per appliance can be integrated.
6) In conjunction with the RC35 programming unit, three function modules can be used in each system.
7) Function module for solar thermal systems for one consumer (solar DHW heating with yield optimisation).
8) The modules can only be installed outside the appliance.
Basic equipment
Optional
Not possible
The WM10 low loss header module and the SM10 solar
module can only be used once per control unit.
Up to three MM10 mixer modules per control unit can be
used.
42
2)
3)
Logamax plus
GB162-15/25/35/45
GB162-25 T40S
5)
5)
5)
8)
6 720 645 821 (2010/09) – Logamax plus GB162
GB162-50/65/80/100
4)
8)