Buderus Logamax plus GB162 Technical Manual page 14

Gas condensing boiler output range from 2.7 kw to 100 kw
Hide thumbs Also See for Logamax plus GB162:
Table of Contents

Advertisement

2
Technical description
GB162-50/65/80/100
18
17
16
15
14
13
GAS VK
AKO
Fig. 9
Function scheme Logamax plus
GB162-50/65/80/100
Key to fig. 6 to fig. 9:
AKO Condensate outlet
AW DHW outlet
EK
Cold water inlet
GAS Gas connection
RK
Boiler return
VK
Boiler flow
RS
DHW cylinder return
VS
DHW cylinder flow
1
Boiler flue connection (flue outlet)
2
Ceramic linear radiant burner
3
Safety temperature sensor
4
ALUplus heat exchanger
5
Return temperature sensor
6
Pressure sensor
7
Modulating high efficiency pump, efficiency category A
8
Logamatic BC10 base controller
9
Universal burner control unit UBA3.5
10
3-way diverter valve
11
Siphon
12
Safety valve
13
Flow temperature sensor
14
Automatic air vent valve
15
Gas valve
16
Venturi nozzle
17
Fan
18
Incandescent ignition and monitoring electrode
19
Sleeve socket for pump installation (UPM 15-70 2W
(accessory) may be integrated)
20
Stratification cylinder (40 l capacity)
21
Cold water inlet sensor
22
DHW temperature sensor
23
Water flow limiter
24
Plate heat exchanger
25
Water flow sensor
26
Cylinder primary pump
27
Drain & fill valve
28
Water flow limiter, adjustable
14
ETA-plus system in the Logamax plus GB162
The ETA-plus system of the Logamax plus GB162 gas
1
condensing boilers minimises the overall running costs
through optimum energy utilisation.
2
Part of the ETA-plus system is a highly effective lamellar
tube heat exchanger with ALUplus technology. It features
an extremely large surface area enabling optimum heat
3
transfer (
4
This concept, which has been proven in millions of
applications, has the following effects:
5
• Year-round utilisation of condensing energy because
6
• A maximum standard seasonal efficiency [to DIN] of up
8
In addition, the Logamax plus GB162 gas condensing
boilers are equipped with a fully pre-mixing ceramic linear
9
radiant burner that modulates its output between 17 %
and 100 %. It is fitted as a downdraught burner above the
RK
lamellar tubes (
6 720 642 463-09.1il
The ETA-plus system is rounded off with a modulating
differential pressure-dependent high efficiency pump in
appliances up to 45 kW (pump for GB162-45 available
as an accessory). This enables simple system hydraulics
without minimum flow rates to be achieved (
Hydraulics Logamax plus GB162-50/65/80/100
The Logamax plus GB162-50/65/80/100 gas
condensing boilers are supplied without integral pumps.
They may be combined with the pump connection
assembly (accessory). The pump connection assembly is
equipped with an output-dependent UPER 25-80 pump.
For the GB162-50, an output-dependent UPM 25-70
high efficiency pump is available as an accessory.
Furthermore, these appliances can be combined on site
with third party differential pressure-dependent pumps.
These should be operated with the setting Δp-v (variable).
fig. 6 to fig. 9, pos. 4).
of the extreme cooling of the flue gases
to 110,5 %
fig. 6 to fig. 9, pos. 2).
6 720 645 821 (2010/09) – Logamax plus GB162
chapter 6).