Buderus Logamax plus GB162 Technical Manual page 35

Gas condensing boiler output range from 2.7 kw to 100 kw
Hide thumbs Also See for Logamax plus GB162:
Table of Contents

Advertisement

Functions and controls on the Logamatic BC10
base controller
• Starting and shutting down the gas condensing boiler
and all connected modules via an ON/OFF switch
(
fig. 25, pos. 1)
• LED showing "DHW heating" (
• DHW temperature setting (
– At position "0", the set DHW temperature is set to
15 °C.
– If the rotary selector is set to between 30 °C and
60 °C, a set DHW temperature is limited by this
rotary selector.
– In the "Aut" setting, the DHW temperature is
selected via the RC35 programming unit.
• LCD to display status and fault diagnosis (
pos. 4)
– Display of boiler water temperature, system
pressure (filling mode) and possibly a fault code
• LED "DHW and CH heat demand" (
• Limitation of the boiler water temperature to a maximum
level (
fig. 25, pos. 6)
• LED "Burner operation" (
• Connection socket for diagnostic plug for connecting
a laptop (
fig. 25, pos. 9)
• "Show status" key for switching the display between
various functions (
fig. 25, pos. 10)
• "Emissions test" key for flue gas test and manual mode
(
fig. 25, pos. 11)
• "Reset" button for resetting the burner in the event of
lockout faults (
fig. 25, pos. 12)
• Emergency operation
• Limiting the output of the gas condensing boiler and
setting system parameters via the software
6 720 645 821 (2010/09) – Logamax plus GB162
fig. 25, pos. 2)
fig. 25, pos. 3)
fig. 25,
fig. 25, pos. 5)
fig. 25, pos. 8)
2
3
4
1
12 11 10 9 8
Fig. 25 Displays/indicators and controls on the
Logamatic BC10 base controller
1
ON/OFF key
2
LED "DHW heating"
3
Rotary selector for setting the DHW temperature
4
LCD to show status, pressure and fault diagnosis
5
LED "DHW and CH heat demand"
6
Rotary selector for limiting the maximum boiler water
temperature
7
RC35 programming unit (optional instead of the fascia)
8
LED "Burner operation (ON/OFF)"
9
Connection socket for diagnostic plug
10
"Status display" key
11
"Emissions test" key for flue gas test and manual mode
12
"Reset" button
Heating control
5
6
7
6 720 642 463-24.1il
4
35

Hide quick links:

Advertisement

Table of Contents
loading