Buderus Logamax plus GB162 Technical Manual page 49

Gas condensing boiler output range from 2.7 kw to 100 kw
Hide thumbs Also See for Logamax plus GB162:
Table of Contents

Advertisement

DHW heating via pump assembly with integral 3-way diverter valve for the Logamax plus GB162-50 and
GB162-65
The 3-way diverter valve can only be fitted to the l.h. side
of the pump connection assembly. The pump connection
assembly with 3-way valve kit is only suitable for Logamax
PZ
KR
EZ
EK
Fig. 41 Logamax plus GB162-50/65 with pump connection assembly and 3-way valve kit
AW
DHW outlet
EK
Cold water inlet
EZ
DHW circulation inlet
FS
Safety temperature sensor
GAS
Gas connection
HK
Heating circuit
KR
Check valve
MAG
Diaphragm expansion vessel
PZ
DHW circulation pump
RK
Boiler return
RS
DHW cylinder return
SMF
Dirt filter
SV
Safety valve
THV
Thermostatic valve
VK
Boiler flow
VS
DHW cylinder flow
1)
On site
6 720 645 821 (2010/09) – Logamax plus GB162
AW
VS
RS
plus GB162-50 and GB162-65, and cannot be used for
boiler sizes 80 kW and 100 kW, as the amount of water
transported by the integral pump is insufficient.
Logamax plus GB162-50/65
FS
SV
SMF
GAS
Δ p [mbar ]
900
800
700
600
500
400
300
200
100
0
0
Fig. 42 Residual head GB162-50/65 with pump
assembly and integral 3-way diverter valve
a
Low load
b
Full load
Δp
Pressure drop
V
Flow rate
DHW heating
1)
MAG
THV
HK
VK
RK
6 720 642 463-29.1il
ΔT = 20 K = 50 kW
b
a
ΔT = 20 K = 65 kW
1000
2000
3000
6 720 642 463-30.1il
5
4000
V [m
3
/h]
49