Buderus Logamax plus GB162 Technical Manual page 54

Gas condensing boiler output range from 2.7 kw to 100 kw
Hide thumbs Also See for Logamax plus GB162:
Table of Contents

Advertisement

6
System examples
Pos.
General design information on hydraulics and control
Observe all building regulations applicable to installation rooms (DVGW-TRGI 2008 [Germany]). Make the gas
connection in line with the technical rules applicable to gas installations. Take any DHW booster heating functions
A
of the appliances into account when sizing the gas flow limiter. The gas connection must only be made by
authorised gas fitters. In addition, the installation of a gas filter in the gas line is also recommended.
Operation in occupied rooms is possible with a balanced flue system or, under certain conditions, with the
B
concentric open flue system GA-X (DVGW-TRGI 2008 [Germany]).
When draining condensate, observe all relevant local waste water ordinances. Frequently installations follow the
C
ATV-DVWK A251 [Germany].
Only operate the Logamax plus GB162 gas condensing boiler in sealed unvented heating systems. Convert open
D
vented systems in accordance with DIN-EN 12828.
"
A "short-circuit
line between the DHW cylinder flow and the DHW cylinder return is required if no separate DHW
S
cylinder is connected to the Logamax plus GB162-15/25/35 gas condensing boilers.
To prevent corrosion damage, never use zinc-plated/galvanised connection lines or fittings in the DHW outlet.
Implement the installation in accordance with DIN 1988 and DIN 4753 (as well as DIN-EN 1717) [or local
regulations]. Observe any orders concerning potable water. A copper-soldered stainless steel plate heat
F
exchanger is part of the Logamax plus GB162-25 T40S.
When connecting the Logamax plus GB162-25 T40S to plastic cold water or DHW lines, observe the methods of
connection with other materials recommended by the manufacturer of the plastic pipe.
G
A stainless steel stratification cylinder with 40 l capacity is integrated into the Logamax plus GB162-25 T40S.
An extensive range of accessories is available for all Logamax plus GB162 gas condensing boilers. There are
1
suitable pipe assemblies to connect the Logamax plus GB162 gas condensing boilers with the Logalux
S135 RW, S160 RW, Logalux S120 W as well as the Logalux SU160 W to SU300 W DHW cylinders.
Observe the pump curve for checking the residual head. The Logamax plus GB162-45/50/65/80/100 appliances
are supplied without internal heating circuit pumps. A UPM 15-70 2W (GB162-45) pump, or the pump connection
assembly (GB162-50/65/80/100) with UPER 25-80, is available for delivery from the factory. These pumps can
be operated in output-dependent mode and, up to 45 kW also in Δp = constant mode. Furthermore, standard
2
differential pressure-dependent pumps can be used outside the appliance. The maximum possible amount of water
via the appliance is as follows:
45 kW = 2500 l/h; 50/65/80/100 kW = 5700 l/h
This must be safeguarded via a line balancing valve.
3
The Logamax plus GB162 can be operated without a minimum flow rate, making an overflow valve superfluous.
For room temperature-dependent or weather-compensated control with room temperature hook-up, install a room
temperature sensor in the reference room of the residential unit. The room temperature sensor is integrated in the
4
RC35 and RC25 programming units. Open all thermostatically controlled radiator valves fully in the reference
room.
A low water indicator is not required when installing the Logamax plus GB162 gas condensing boiler as an attic
5
heating centre. The function of a thermostatically controlled low water indicator is safeguarded with a minimum
pressure switch inside the appliance and is verified by type testing.
A dirt trap is not required if a new system is thoroughly flushed prior to commissioning, and oxygen corrosion
6
(loose particles) can be prevented. Older systems must always be flushed; the installation of a dirt trap is also
highly recommended.
A boiler drain & fill valve (FE) is included in the heating circuit connection set (accessory). In addition we
7
recommend providing a drain facility at the lowest point of the system.
Table 22 Information regarding the sample circuit diagrams (
the Logamax plus GB162
54
fig. 46 and fig. 47, page 53) for all systems that include
6 720 645 821 (2010/09) – Logamax plus GB162
Further
information
Page 30
Page 109 f.
Page 109 f.
Page 111 f.
Page 85
Page 30
Page 56 f.
Page 71
Page 87 f.
Pages 87 ff.
Page 60 f.
Page 58
Page 32
Page 36
Page 37
Page 9 ff.
Page 56
Pages 87 ff.