Fan Speed Control For Indoor Unit - Daikin 2MXS-N Series Service Manual

Hide thumbs Also See for 2MXS-N Series:
Table of Contents

Advertisement

SiUS121502E
1.4

Fan Speed Control for Indoor Unit

Outline
Phase control and fan speed control contains 9 steps: LLL, LL, SL, L, ML, M, MH, H, and HH.
The airflow rate can be automatically controlled depending on the difference between the room
thermistor temperature and the target temperature.
Automatic Fan
In automatic fan speed control, the step SL is not available.
Speed Control
LLL
LL
L
ML
M
MH
H
HH (POWERFUL)
<Cooling>
The following drawing explains the principle of fan speed control for cooling.
*The upper limit is M tap in 30 minutes from the operation start.
<Heating>
In heating operation, the fan speed is regulated according to the indoor heat exchanger
temperature and the difference between the room thermistor temperature and the target
temperature.
Note:
The fan stops during defrost operation.
COMFORT
CTXS, FTXS Series
AIRFLOW
Operation
Function and Control
Step
= The airflow rate is automatically controlled within this range when the FAN button is set to
automatic.
Fan speed
+2.5°C (+4.5°F)
+1.5°C (+2.7°F)
+0.5°C (+0.9°F)
The fan speed is controlled automatically within the following steps.
<Cooling>
L tap ~ MH tap (same as AUTOMATIC)
<Heating>
ML tap ~ MH tap
The latest command has the priority between POWERFUL and COMFORT AIRFLOW.
Function of CTXS, FTXS, CDXS, FDXS, FVXS Series
Cooling
Heating
(R11681)
(R6834)
Room thermistor temperature – target temperature
MH*
+3°C (+5.4°F)
M
+2°C (+3.6°F)
ML
+1°C (+1.8°F)
L
(R21654)
39