Fan Speed Control For Indoor Unit - Daikin FTX-N Series Service Manual

Inverter pair: wall mounted type, floor standing type, duct connected type.
Hide thumbs Also See for FTX-N Series:
Table of Contents

Advertisement

SiUS091601EA
2.3

Fan Speed Control for Indoor Unit

Outline
Phase control and fan speed control contains 9 steps: LLL, LL, SL, L, ML, M, MH, H, and HH.
The airflow rate can be automatically controlled depending on the difference between the room
thermistor temperature and the target temperature.
Automatic Fan
In automatic fan speed operation, the step SL is not available.
Speed Control
to automatic.
 Cooling
The following drawing explains the principle of fan speed control for cooling.
The upper limit is at M tap in 30 minutes from the operation start.
 Heating
In heating operation, the fan speed is regulated according to the indoor heat exchanger
temperature and the difference between the room thermistor temperature and the target
temperature.
Note(s)
The fan stops during defrost operation.
Part 4 Functions and Control
Step
LLL
LL
L
ML
M
MH
H
HH (POWERFUL)
= The airflow rate is automatically controlled within this range when FAN setting button is set
Fan speed
+2.5°C (+4.5°F)
+1.5°C (+2.7°F)
+0.5°C (+0.9°F)
Functions for FTX, FVXS Series
Cooling
Heating
Room thermistor temperature – target temperature
MH*
+3°C (+5.4°F)
M
+2°C (+3.6°F)
ML
+1°C (+1.8°F)
L
R4003512
(R21654)
50