Daikin 2MXS52E2V1B Installation Manual
Daikin 2MXS52E2V1B Installation Manual

Daikin 2MXS52E2V1B Installation Manual

R410a split series
Hide thumbs Also See for 2MXS52E2V1B:

Advertisement

INSTALLATION
MANUAL
R410A Split Series
Models
2MXS52E2V1B
3MXS52E2V1B
3AMX52E2V1B
2MXS52E3V1B
3MXS52E3V1B
3AMX52E3V1B
2AMX52E2V1B
3MKS50E2V1B
4MKS58E2V1B
2AMX52E3V1B
3MKS50E3V1B
4MKS58E3V1B
Installation manual
R410A Split series
Installationsanleitung
Split-Baureihe R410A
Manuel d'installation
Série split R410A
Montagehandleiding
R410A Split-systeem
Manual de instalación
Serie Split R410A
Manuale d'installazione
Serie Multiambienti R410A
Εγχειρßδιο εγκατÜστασηò
διαιροýìενηò σειρÜò R410A
Manual de Instalação
Série split R410A
Рóêоводство по монтажó
Серия R410A с раздельной óстановêой
Montaj kýlavuzlarý
R410A Split serisi
English
Deutsch
Français
Nederlands
Español
Italiano
ΕλληνικÜ
Portugues
Рóссêий
Türkçe

Advertisement

Table of Contents
loading

Summary of Contents for Daikin 2MXS52E2V1B

  • Page 1 R410A Split-systeem Manual de instalación Español Serie Split R410A Manuale d’installazione Italiano Serie Multiambienti R410A Εγχειρßδιο εγκατÜστασηò Models ΕλληνικÜ διαιροýìενηò σειρÜò R410A 2MXS52E2V1B 2AMX52E2V1B Manual de Instalação 3MXS52E2V1B 3MKS50E2V1B Portugues Série split R410A 3AMX52E2V1B 4MKS58E2V1B Рóêоводство по монтажó 2MXS52E3V1B 2AMX52E3V1B Рóссêий...
  • Page 2 2SB63475-13K...
  • Page 3: Safety Precautions

    Safety Precautions • Read these Safety Precautions carefully to ensure correct installation. • This manual classifies the precautions into WARNING and CAUTION. Be sure to follow all the precautions below: they are all important for ensuring safety. WARNING....Failure to follow any of WARNING is likely to result in such grave consequences as death or serious injury. CAUTION....Failure to follow any of CAUTION may in some cases result in grave consequences.
  • Page 4: Precautions For Selecting The Location

    Accessories Accessories supplied with the outdoor unit: (B) Drain plug (A) Installation Manual There is on the bottom packing case. (D) Screw bag (C) Reducer assy (For fixing electrical wire anchor bands) There is on the bottom packing case. (2MXS52∗, 2AMX52∗, 3MXS52∗, 3AMX52∗, 4MKS58∗) There is on the bottom packing case.
  • Page 5: Indoor/Outdoor Unit Installation Drawings

    Indoor/Outdoor Unit Installation Drawings For installation of the indoor units, refer to the installation manual which was provided with the units. (The diagram shows a wall-mounted indoor unit.) CAUTION 1) Do not connect the embedded branch piping and the outdoor unit when only carrying out piping work without connecting the indoor unit in order to add another indoor unit later.
  • Page 6: Connections (Connection Port)

    Installation • Install the unit horizontally. • The unit may be installed directly on a concrete verandah or a solid place if drainage is good. • If the vibration may possibly be transmitted to the building, use a vibration-proof rubber (field supply). Connections (connection port) Install the indoor unit according to the table below, which shows the relationship between the class of indoor unit and the corresponding port.
  • Page 7: Outdoor Unit Installation Guideline

    Outdoor Unit Installation Guideline • Where a wall or other obstacle is in the path of outdoor unit’s intake or exhaust airflow, follow the installation guidelines below. • For any of the below installation patterns, the wall height on the exhaust side should be 1200mm or less. Walls facing two sides Wall facing one side More than 100...
  • Page 8: Refrigerant Piping Work

    Refrigerant Piping Work Installing outdoor unit 1) When installing the outdoor unit, refer to “Precautions for Selecting the Location” and the “Indoor/Outdoor Unit Installation Drawings”. 2) If drain work is necessary, follow the procedures below. Drain work 1) Use drain plug for drainage. 2) If the drain port is covered by a mounting base or floor surface, place Drain-water hole additional foot bases of at least 30mm in height under the outdoor...
  • Page 9: Purging Air And Checking Gas Leakage

    Refrigerant Piping Work Purging air and checking gas leakage 1) When piping work is completed, it is necessary to purge the air and check for gas leakage. WARNING 1) Do not mix any substance other than the specified refrigerant (R410A) into the refrigeration cycle. 2) When refrigerant gas leaks occur, ventilate the room as soon and as much as possible.
  • Page 10: Charging With Refrigerant

    Refilling the refrigerant Check the type of refrigerant to be used on the machine nameplate. Precautions when adding R410A Fill from the liquid pipe in liquid form. It is a mixed refrigerant, so adding it in gas form may cause the refrigerant composition to change, preventing normal operation. 1) Before filling, check whether the cylinder has a siphon attached or not.
  • Page 11 Refrigerant Piping Work Flaring the pipe end (Cut exactly at 1) Cut the pipe end with a pipe cutter. right angles.) Remove burrs 2) Remove burrs with the cut surface facing down- Flaring ward so that the chips do not enter the pipe. Set exactly at the position shown below.
  • Page 12: How To Use Reducers

    How to Use Reducers No.1 No.2 No.3 No.4 No.5 No.6 φ15.9 φ12.7 φ15.9 φ12.7 φ15.9 φ15.9 → φ12.7 → φ9.5 → φ12.7 → φ9.5 → φ9.5 → φ9.5 Gasket (1) Gasket (2) Reduce and gasket Use the reducers supplied with the unit as described below. 1) Connecting a pipe of φ12.7 to a gas pipe connection port for φ15.9: No.
  • Page 13: Pump Down Operation

    Pump Down Operation In order to protect the environment, be sure to pump down when relocating or disposing of the unit. 1) Remove the valve lid from liquid shut-off valve and gas shut- off valve. Close Gas shut-off valve 2) Carry out forced cooling operation. Hexagonal 3) After five to ten minutes, close the liquid shut-off valve with a wrench...
  • Page 14 Wiring WARNING 1) Do not use tapped wires, stand wires, extensioncords, or starbust connections, as they may cause overheating, electrical shock, or fire. 2) Do not use locally purchased electrical parts inside the product. (Do not branch the power for the drain pump, etc., from the terminal block.) Doing so may cause electric shock or fire.
  • Page 15: Priority Room Setting

    Priority Room Setting • To use priority room setting, initial settings must be made when the unit is installed. Explain the priority room setting, as described below, to the customer, and confirm whether or not the customer wants to use priority room setting. Setting it in the guest and living rooms is convenient.
  • Page 16: Night Quiet Mode Setting

    Night Quiet Mode Setting • If night quiet mode is to be used, initial settings must be made when the unit is installed. Service PC-board Explain night quiet mode, as described below, to the customer, and confirm whether or not the customer wants to use night quiet mode.
  • Page 17: Test Run And Final Check

    Test Run and Final Check • Before starting the test run, measure the voltage at the primary side of the safety breaker. Check that it is 220-240V. • Check that all liquid and gas shut-off valves are fully open. • Check that piping and wiring all match. The wiring error check can be conveniently used for underground wiring and other wiring that cannot be directly checked.
  • Page 18: Items To Check

    Test run and final check 1) To test cooling, set for the lowest temperature. To test heating, set for the highest temperature. (Depending on the room temperature, only heating or cooling (but not both) may be possible.) 2) After the unit is stopped, it will not start again (heating or cooling) for approximately 3 minutes. 3) During the test run, first check the operation of each unit individually.
  • Page 19 3P164392-2E M05B110A (0606) HT...

Table of Contents