6.8
Signal Transmission Error (Between MAIN Remote
Controller and SUB Remote Controller)
U8
Error Code
Method of Error
In case of controlling with 2 remote controllers, check the system using microcomputer if signal
transmission between MAIN remote controller and SUB remote controller is normal.
Detection
Error Decision
Normal transmission does not continue for specified period.
Conditions
Supposed
Causes
Troubleshooting
134
Remote controller is set to SUB when using 1 remote controller
Connection of 2 sub remote controllers (when using 2 remote controllers)
Defective remote controller PCB
Be sure to turn off the power switch before connecting or disconnecting
Caution
connectors, or parts may be damaged.
NO
Using 2 remote
controllers?
YES
Is SS1 of both
NO
remote controllers
set to SUB?
YES
Is SS1
NO
of remote
controller PCB set to
SUB?
YES
SiUS121502E
Set SS1 to MAIN; turn the
power supply off once and then
back on.
Turn the power off and then
back on. If a malfunction occurs,
replace the remote controller
PCB.
Turn the power off and then
back on. If a malfunction occurs,
replace the remote controller
PCB.
Set one remote controller to
MAIN; turn the power supply off
once and then back on.
(R21113)