Electrical Box Temperature Rise - Daikin 2MXS-N Series Service Manual

Hide thumbs Also See for 2MXS-N Series:
Table of Contents

Advertisement

Troubleshooting for Outdoor Unit

7.18 Electrical Box Temperature Rise

L3
Error Code
Outdoor Unit LED
A
Display
Method of Error
An electrical box temperature rise is detected by checking the radiation fin thermistor with the
compressor off.
Detection
Error Decision
Conditions
100°C (212°F)
Supposed
Causes
Troubleshooting
Check No.17
Refer to P.173
Check No.19
Refer to P.174
162
j
i
i
h
i
1
2
3
4
With the compressor off, the radiation fin temperature is above
The error is cleared when the temperature drops below
To cool the electrical components, the outdoor fan starts when the radiation fin temperature
rises above
and stops when it drops below
C
A
B
70°C (158°F)
Defective outdoor fan motor
Short circuit
Defective radiation fin thermistor
Disconnection of connector
Defective outdoor unit PCB
Be sure to turn off the power switch before connecting or disconnecting
Caution
connectors, or parts may be damaged.
Turn off the power. Then, turn on
the power to restart the system.
Error again or outdoor
fan activated?
NO
Check No. 19
Check the outdoor fan.
OK
Radiation fin dirty?
YES
h
5
.
B
C
85°C (185°F)
To cool the electrical components,
the outdoor fan starts when the
radiation fin temperature rises
above C. The outdoor fan stops
when the radiation fin temperature
drops below B.
YES
Check the radiation fin
temperature.
Above A?
YES
NG
NO
.
A
.
B
WARNING
NO
Replace the outdoor unit
PCB (main PCB).
Replace the outdoor fan
motor.
Correct the connectors
and fan motor lead wire.
Replace the outdoor unit
PCB (main PCB).
Check the installation
condition.
Go to Check No. 17.
Clean up the radiation fin.
Service Diagnosis
SiUS121502E
(R22272)