Discharge Pipe Temperature Control - Daikin 2MXS-N Series Service Manual

Hide thumbs Also See for 2MXS-N Series:
Table of Contents

Advertisement

Troubleshooting for Outdoor Unit

7.12 Discharge Pipe Temperature Control

F3
Error Code
Outdoor Unit LED
A
Display
Method of Error
An error is determined with the temperature detected by the discharge pipe thermistor.
Detection
Error Decision
Conditions
18 class
24/36 class
Supposed
Causes
Troubleshooting
Check No.01
Refer to P.166
Check No.12
Refer to P.169
Check No.14
Refer to P.170
152
j
i
h
i
h
1
2
3
4
If the temperature detected by the discharge pipe thermistor rises above
stops.
The error is cleared when the discharge pipe temperature is dropped below
A
120°C (248°F)
120°C (248°F)
If the error repeats, the system is shut down.
Reset condition: Continuous run for about 60 minutes without any other error
Defective discharge pipe thermistor
(Defective outdoor heat exchanger thermistor or outdoor temperature thermistor)
Defective electronic expansion valve or coil
Refrigerant shortage
Defective four way valve
Water mixed in refrigerant
Defective stop valve
Defective outdoor unit PCB
Be sure to turn off the power switch before connecting or disconnecting
Caution
connectors, or parts may be damaged.
Check No. 01
Check the thermistors.
OK
Check No. 12
Check the electronic
expansion valve.
OK
Check No. 14
Check the refrigerant line.
OK
h
5
B
95°C (203°F)
107°C (224.6°F)
NG
Discharge pipe thermistor
Outdoor heat exchanger thermistor
Outdoor temperature thermistor
NG
NG
Refrigerant shortage
Four way valve
Water mixed
Stop valve
SiUS121502E
, the compressor
A
B.
Replace the
defective
thermistor(s).
Replace the electronic
expansion valve or the coil.
Refer to the refrigerant line
check procedure.
Replace the outdoor unit
PCB (main PCB).
(R20417)
Service Diagnosis