8-3. Table Inspection of outdoor unit main parts

No.
Parts name
1
Compressor
(Model : DA150A1T-20F)
2
Fan motor
(Model : ICF-140-43-4R)
3
Compressor
(Model : DA330A2T-20M)
4
Outdoor fan motor
(Model : WDF-340-A100-1)
5
4-way valve coil
(Cooling/heating switching)
(Model : STF-H)
SVM-13072.indb 72
SVM-13072.indb 72
Checking procedure
Measure the resistance value of each winding by using the tester.
Red
White
Black
Measure the resistance value of each winding by using the tester.
Red
White
Black
Measure the resistance value of each winding by using the tester.
Red
White
Black
Measure the resistance value of each winding by using the tester.
Red
White
Black
Measure the resistance value of each winding by using the tester.
Connector : White
– 72 –
FILE NO. SVM-13072
Position
Resistance value
Red – White
1.03 Ω
White – Black
Black – Red
Under 20°C
Position
Resistance value
Red – White
21.00±1.05 Ω
White – Black
Black – Red
Under 20°C
Position
Resistance value
Red – White
0.37 Ω
White – Black
Black – Red
Under 20°C
Position
Resistance value
Red – White
17.3±1.7 Ω
White – Black
Black – Red
Under 20°C
Resistance value
7.1±0.36 Ω
Under 20°C