Table Inspection Of Outdoor Unit Main Parts - Toshiba RAV-GM1101AT8P-E Service Manual

Outdoor unit digital r32 inverter
Hide thumbs Also See for RAV-GM1101AT8P-E:
Table of Contents

Advertisement

8-3. Table Inspection of outdoor unit main parts

No.
Parts name
1
Compressor
(Model : RX330A2T-20M)
Outdoor fan motor
2
(Model : WDF-340-A100-1)
4-way valve coil
3
(Cooling/heating switching)
(Model : STF-H)
Measure the resistance value of each winding by using the tester.
Red
White
Black
Measure the resistance value of each winding by using the tester.
Red
White
Black
Measure the resistance value of each winding by using the tester.
Connector : White
- 63 -
Checking procedure
Position
Red – White
White – Black
Black – Red
Position
Red – White
White – Black
Black – Red
Resistance value
7.1±0.36 Ω
FILE NO.SVM-18044-2
Resistance value
1.20 Ω
Under 20°C
Resistance value
17.3±1.7 Ω
Under 20°C
Under 20°C