Remote Controller Wiring; Address Setup (Manual Setting From Remote Controller) - Toshiba RAV-SM564ATJP-E Service Manual

Air-conditioner (split type)
Table of Contents

Advertisement

10-3. Remote Controller Wiring

Strip off approx. 9 mm the wire to be connected.
For single system, use non polarity, 2 core wire is
used for wiring of the remote controller.
(0.5 mm² to 2.0 mm² wires)
For the synchronous twin, triple system, use
2-conre shield wire (Vinyl cord for microphone 0.5
to 2.0 mm²) to conform to the EMC standard.
Single system
Remote controller
Remote controller wiring
Indoor side
Indoor/Outdoor
connecting wires
Outdoor side
10-4. Address Setup
In case that addresses of the indoor units will be
determined prior to piping work after cabling work
Set an indoor unit per a remote controller.
Turn on power supply.
SVM-13072.indb 89
SVM-13072.indb 89
A
B
1
2
3
1
2
3
L
N
Power supply
(Manual setting from remote controller)
Indoor unit address
Group address
Wiring diagram
Terminal block for remote controller
wiring of indoor unit
A
B
Remote controller wire
(Procured locally)
∗ For details of wiring/installation of the remote
controller, refer to the Installation Manual enclosed
with the remote controller.
Simultaneous twin system
Remote controller
Remote controller wiring
Indoor side
Indoor/Outdoor
connecting wires
Outdoor side
(Example of 2-lines cabling)
(Real line: Cabling, Broken line: Refrigerant pipe)
Outdoor
1 2 3
1 2 3
1 2 3
Indoor
Indoor
A B
A B
1
Line address
1
2
1
2
1
A B
Remote controller
For the above example, perform setting by
connecting singly the wired remote controller
without remote controller inter-unit cable.
Group address
Individual
: 0000
Master unit : 0001
Sub unit
: 0002
– 89 –
FILE NO. SVM-13072
Terminal block
Remote controller
A
unit
B
A
B
1
2
3
1
2
3
L
N
Power supply
Outdoor
1 2 3
1 2 3
1 2 3
Indoor
Indoor
A B
A B
2
2
1
2
2
2
In case of group control
11/01/13 1:53 PM
11/01/13 1:53 PM