10. Defrost control
1 In heating operation, defrost operation is performed when TE sensor temperature satisfies any condition in
A zone to D zone.
2 The defrost operation is immediately finished if TE sensor temperature has become 12°C continuing for
3 seconds or more, or it also is finished when condition of 7°C < TE < 12°C has continued for 1 minute.
The defrost operation is also finished when defrost operation has continued for 10 minutes even if TE
sensor temperature has become 7°C or lower.
3 After defrost operation has finished, the compressor and the outdoor fan start heating operation after
stopped for approx. 40 seconds.
Start of heating operation
TE [°C]
* From 10 minutes to 15 minutes after a heating operation started, the minimum value of TE is stored in
memory as TEO and the minimum temperature of TO as ToO.
A zone
B zone
C zone
D zone
a
b
c
d
11. High-pressure switch
1) When the high-pressure switch operates, the operation of the compressor is terminated.
2) The compressor restarts after 5 minutes using [1] as an error count.
After restart, the error count is cleared when operation continues for 10 minutes or more.
3) An error is confirmed with the error count [10].
4) For the indicated contents of error, confirm using the check code table.
12. Control of compressor case thermo
1) The compressor stops when the case thermo of the compressor operated.
2) When the case thermo operated for approx. 80 seconds, H04 error code is displayed on the
wired remote controller. → Refer to the Check Code.
3) When the case thermo is reset, the operation restarts.
SVM-13072_001-050.indd 44
SVM-13072_001-050.indd 44
0
15
10
-2
-10
-13
-18
*
At normal TO
When status of [(TEO – TE) – (ToO – TO) ≥ 3
continued for 20 seconds
When status of [(TEO – TE) – (ToO – TO) ≥ 2
continued for 20 seconds
When status of [SM56, 80 : TE ≤ – 25
When compressor operation status with SM56, 80 : TE < – 13
SM56, 80
SM110, 140
41
29
29
90
c
a
b
A zone
B zone
C zone
When status of [(TEO – TE) ≥ 3
˚
C]
continued for 20 seconds
When status of [(TEO – TE) ≥ 2
˚
C]
continued for 20 seconds
C, SM110,140 : TE ≤ –18
˚
are added by d times
55
45
39
150
– 44 –
FILE NO. SVM-13072
d [min.]
SM56,80
SM110,140
D zone
At error TO
˚
C]
˚
C]
˚
C] continued for 20 seconds
C, SM110,140 : TE < – 2
˚
˚
C
11/01/13 2:59 PM
11/01/13 2:59 PM