8-3. Table Inspection of outdoor unit main parts

No.
Parts name
1
Compressor
(Model : DA150A1T-20F)
Compressor
2
(Model :
DA131S1B-31FZ)
Fan motor
3
(Model : ICF-140-43-4R)
4-way valve coil
4
(Cooling/heating switching)
(Model : STF)
Measure the resistance value of each winding by using the tester.
Red
White
Black
Measure the resistance value of each winding by using the tester.
Red
White
Black
Measure the resistance value of each winding by using the tester.
Red
White
Black
Measure the resistance value of each winding by using the tester.
Connector : White
– 63 –
Checking procedure
Position
Red – White
White – Black
Black – Red
Position
Red – White
White – Black
Black – Red
Position
Red – White
White – Black
Black – Red
Resistance value
1435±144 Ω
FILE NO. SVM-14059
Resistance value
1.04 to 1.16 Ω
Under 20°C
Resistance value
1.70 Ω
Under 20°C
Resistance value
21.00±1.05 Ω
Under 20°C
Under 20°C