Optional Equipment
7
Place the included propane label over the natural gas
label on top of the gas control valve.
8
With the glass removed, bleed the gas line (if applicable) and start the pilot (see the directions on page
37). Leak-test all gas connections and the regulator. Check the pilot. Adjust if necessary. Replace
the glass and face.
WARNING:
When lighting or re-lighting the pilot, the glass must be removed (see
page 37).
To adjust the pilot flame,
remove the cover screw
and gasket and turn the
needle valve (NOTE: if
the needle valve is totally
unscrewed, gas will come
out of this port).
Clockwise lowers the
Cover Screw Gasket
flame while counter-
clockwise raises it.
Replace the cover screw
and gasket.
Remote Thermostat
!
Do not connect 110-120 VAC to the gas control valve or wiring system of this unit.
Follow the instructions included with the remote thermostat for installation.
IMPORTANT OPERATIONAL NOTE FOR REMOTE THERMOSTAT USE:
Included with the remote thermostat is a set of instructions that should be given to the homeowner.
Please be aware that the remote thermostat has a 1 to 2 minute lag time between the time the
thermostat is turned up and the heater turns on.
Travis Industries
PILOT ADJ
Cover Screw
Standard
Screwdriver
(Part # 99300651)
4 0 2 0 8 1 2
(for qualified installers only)
The pilot flame must contact the thermocouple and
thermopile (see the illustration below). Adjust the pilot up or
down as necessary.
Needle Valve
Micro (1/16")
Standard
Screwdriver
4 9
THIS CONTROL
HAS BEEN
CONVERTED TO
LP
9 3 5 0 8 1 1 0