3 Technical Specifications

3.1 Type Test Specifications

IEC 61000-6-2 EMC: Generic Standards - Immunity for industrial environments
Test
IEC 61000-4-2
IEC 61000-4-3
IEC 61000-4-4
IEC 61000-4-5
IEC 61000-4-6
(Conducted) RFI
IEC 61000-4-8
IEC 61000-4-11
IEC 61000-4-12
Damped Oscillatory
Mains Frequency
IEC 61000-4-16
IEC 61000-4-17
Table 7: Electromagnetic Compatibility tests
Test
IEC 60068-2-1
Cold Temperature
IEC 60068-2-2
IEC 60068-2-30
IEC 60255-21-1
IEC 60255-21-2
Table 8: Environmental Type Tests
RuggedSwitch™i800 family
Description
Enclosure Contact
ESD
Radiated RFI
Burst (Fast
Transient)
Surge
Induced
Earth ground ports
Magnetic Field
Voltage Dips
Voltage
Ripple on D.C.
Power Supply
IEC Environmental Type Tests
Description
Dry Heat
Humidity (Damp
Heat, Cyclic)
Vibration
Shock
Enclosure Air
Enclosure ports
Signal ports
DC Power ports
Signal ports
DC Power ports
Signal ports
DC Power ports
Enclosure ports
DC Power ports
Signal ports
DC Power ports
Signal ports
DC Power ports
DC Power ports
Test Ad
Test Bd
Test Db
Tests Fc
Tests Ea
17
Technical Specifications
Levels
+/- 4kV
+/- 8kV
10 V/m, 80 to 1000Mhz
+/- 1kV @ 5kHz
+/- 1kV @ 5kHz
+/- 1kV line-to-earth/line
+/- 0.5kV line-to-line
+/- 1kV line-to-earth
10V @ 0, 5-80 MHz
30 A/m @ 50, 60 Hz
30% reduction for 0.5 period
1kV common mode
0.5kV differential mode
10V continuous
100V for 1s
10%
Test Levels
-40°C, 16 Hours
+85°C, 16 Hours
95% (non-condensing), 55°C , 6
cycles
1g @ (10 - 500) Hz
30g @ 11mS