Refrigerant Charge - Carrier 48PG03-16 Controls, Start-Up, Operation, Service And Troubleshooting Instructions

Single package small rooftop units with comfort link controls and puron (r---410a) refrigerant
Hide thumbs Also See for 48PG03-16:
Table of Contents

Advertisement

Refrigerant Charge

Amount of refrigerant charge is listed on unit nameplate. Refer to
Carrier GTAC II; Module 5; Charging, Recovery, Recycling, and
Reclamation section for charging methods and procedures. Unit
panels must be in place when unit is operating during charging
procedure.
Puron® (R-410A) refrigerant systems should be charged with
liquid refrigerant. Use a commercial type metering device in the
manifold hose.
WARNING
!
UNIT OPERATION AND SAFETY HAZARD
Failure to follow this warning could cause personal
injury, death and/or equipment damage.
Puron (R- -410a) refrigerant systems operate at higher
pressures than standard R- -22 systems. Do not use R- -22
service equipment or components on Puron refrigerant
equipment. Gauge set, hoses, and recovery system must
be designed to handle Puron refrigerant.
about equipment, consult the equipment manufacturer.
NOTE:
Do not use recycled refrigerant as it may contain
contaminants.
No Charge
Use standard evacuating techniques. After evacuating system,
weigh in the specified amount of refrigerant (refer to unit
nameplate).
NOTE: System charge for units with Humidi-MiZer™ system is
greater than the system charge of the standard unit.
Low Charge Cooling
Using cooling charging chart (see Fig. 47-55), add or remove
refrigerant until conditions of the chart are met. An accurate
pressure gauge and temperature-sensing device is required.
Charging is accomplished by ensuring the proper amount of
liquid subcooling. Connect pressure gauge to the compressor
discharge service valve. Connect temperature sensing device to
the liquid line between the condenser and the TXV (thermostatic
expansion valve), and insulate it so that ambient temperature does
not affect reading.
To Use the Cooling Charging Chart, Standard Unit
NOTE: All circuits must be running in normal cooling mode.
Indoor airflow must be within specified air quantity limits for
cooling. (See Table 79.) All outdoor fans must be on and
running at high speed. Use the Cooling Service Test Outdoor Fan
Override function to start all outdoor fans.
If unsure
116
R410A REFRIGERA
R410A
REFRIGERANT
OUTDOOR
OUTDOOR FAN
FAN MUST
MUST BE
BE OPERATING
OPERATING ON
160
160
140
140
Add
dd Charge
Charge if if Above
bove the
the Curve
Curve
120
120
100
100
80
80
Remove
Remo
ve Charge
Charge if if Below
60
60
40
40
20
20
150
150
200
200
250
250
300
300
350
350
400
400
Comp
Compressor
ressor Disch
Discharge
arge Pressu
Pressure,
Fig. 47 --- Charging Chart — 48/50PG03
R4
R410A RE
REFRI RIGERANT
OUTDOOR F
R FAN M
N M UST BE OPERATING ON H
160
16
14
140
12
120
Add Cha
harge
ge if Abov
bove the
the Cur urve
100
10
80
80
Rem ove Charge if Be
Re
60
60
40
40
20
20
150
150
200
200
250
250
300
300
350
350
400
400
Compre ss
ssor Disc
isc ha rge P re ss
Fig. 48 --- Charging Chart — 48/50PG04
NT
ON HIGH
HIGH SPEED
SPEED
Below the
the Curve
Curve
450
450
500
500
550
550
600
600
re, [p [psig
sig]
C07038
RANT
N HIGH S
H SPEED
Below the Curve
450
450
500
500
550
550
600
600
ssure , [psig
sig]
C07039

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

50pg03-16

Table of Contents