APPENDIX A — LOCAL DISPLAY AND CCN TABLES (CONT)
ITEM
EXPANSION
CONFIGURATION (cont)
AIR.Q
Air Quality Configuration
IA.CF
IAQ Analog Input Config
IA.FN
IAQ Analog Fan Config
II.CF
IAQ Switch Input Config
II.FN
IAQ Switch Fan Config
AQ.MN
Econo Min IAQ Position
EC.MN
Econo Minimum Position
OVR.P
IAQ Override Position
OA.CF
OAQ Analog Input Cfg
OAQ.L
OAQ Lockout Limit
AQD.L
AQ Differential Low
AQD.H
AQ Differential High
DF.ON
Fan On AQ Differential
DF.OF
Fan Off AQ Differential
I.4M
IAQ Sensor Value at 4mA
I.20M
IAQ Sensor Value at 20mA
O.4M
OAQ Sensor Value at 4mA
O.20M
OAQ Sensor Value at 20mA
H.4M
RH Sensor Value at 4mA
H.20M
RH Sensor Value at 20mA
ALM.O
Alarm Relay Configuration
A.SPC
SPT/SPRH Sensor Failure
A.SRT
SAT/RAT Sensor Failure
A.OAT
OAT Thermistor Failure
A.CS
Current Sensor Failure
A.CMP
Compressor Failure
A.CKT
Refrigerant Circuit Failure
A.SSP
SSP Transducer Failure
A.SCT
SCT Thermistor Failure
A.FAN
Indoor Fan Failure
A.FIL
Dirty Filter
A.TST
Thermostat Failure
A.ECO
Economizer Failure
TRIM
Sensor Calibration
SPT.C
Space Temp Calibration
SPT.T
Space Temp Trim
SAT.C
Supply Air Temp Calib.
SAT.T
Supply Air Temp Trim
RAT.C
Return Air Temp Calib.
RAT.T
Return Air Temp Trim
CCN
CCN Configuration
CCN.A
CCN Element Number
CCN.B
CCN Bus Number
BAUD
CCN Baud Rate
BROD
CCN Broadcast Configuration
B.TIM
CCN Time/Date Broadcast
B.OAT
CCN OAT Broadcast
B.GS
Global Schedule Broadcast
B.ACK
CCN Broadcast Ack'er
SCH.O
CCN Schedule Overrides
SCH.N
Schedule Number
HOL.G
Accept Global Holidays
OV.TL
Override Time Limit
OV.EX
Timed Override Hours
OV.SP
SPT Override Enabled
LEGEND
FIOP --- --- Factory ---Installed Option
MODE — CONFIGURATION (cont)
RANGE
UNITS
0=No IAQ
1=Demand Ventilation
2=Econ Position Override
3=Econ Min Position Control
0=Never
1=Only While Occupied
2=Always
0=No IAQ
1=DCV Normally Open
2=DCV Normally Closed
3=Override Normally Open
4=Override Normally Closed
0=Never
1=Only While Occupied
2=Always
0 to 100
0 to 100
0 to 100
0=No OAQ
1=Demand Ventilation
2=Outdoor Air Lockout
0 to 5000
0 to 5000
0 to 5000
0 to 5000
0 to 5000
0 to 5000
0 to 5000
0 to 5000
0 to 5000
0 to 50
%
60 to 100
%
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
–30 to 120
dF
–30 to 30
^F
–30 to 130
dF
–30 to 30
^F
–30 to 130
dF
–30 to 30
^F
1 to 239
0 to 239
1=2400
2=4800
3=9600
4=19200
5=38400
Yes/No
Yes/No
Yes/No
Yes/No
0=Always Occupied
1 to 64=Local Schedule
65 to 99=Global Schedule
Yes/No
0 to 4
hours
0 to 4
hours
Yes/No
CCN
DEFAULT
TABLE/SUB-TABLE
0: no FIOP
1: FIOP
0
0
0
10
30
IAQ_CFG
IAQ_CFG
100
0
600
100
700
600
200
0
2000
0
2000
0
100
Yes
Yes
Yes
Yes
Yes
Yes
ALM CFG
ALM_CFG
Yes
Yes
Yes
Yes
Yes
Yes
0
(CCN TRIM — see
(CCN TRIM — see
Maintenance Display)
Maintenance Display)
0
0
CONFIGURATION
1
(not in CCN table)
0
(not in CCN table)
3
(not in CCN table)
No
No
BRODEFS
BRODEFS
No
No
0
SCHEDOVR
SCHEDOVR
No
1
0
Yes
129
PAGE
CCN POINT
NO.
IAQANCFG
59, 72,
111
IAQANFAN
62, 72, 75
IAQINCFG
59, 72,
74
IAQINFAN
62, 75
IAQMINP
72
ECONOMIN
72, 75
IAQOVPOS
72, 74
OAQANCFG
72, 74,
111
OAQLOCK
74
DAQ_LOW
72
DAQ_HIGH
72
DAQFNON
75
DAQFNOFF
75
IAQ_4MA
72
IAQ_20MA
72
OAQ_4MA
74
OAQ_20MA
74
RH_4MA
69
RH_20MA
69
76
SPACE_AL
SATRATAL
OAT_AL
CS_AL
COMP_AL
CKT_AL
SSP_AL
SCT_AL
FAN_AL
FILT_AL
TSTAT_AL
ECON_AL
88
88
88
88
88
54, 75
54, 75
54, 75
CCNBC
75
OATBC
75
GSBC
61, 75
CCNBCACK
76
SCHEDNUM
55, 61, 62,
76
HOLIDAYT
76
OTL
76
OVR_EXT
62, 76
TIMEOVER
62, 76

Hide quick links: