APPENDIX A — LOCAL DISPLAY AND CCN TABLES (CONT)
DISPLAY MENU/
EXPANDED
SUB-MENU/NAME
SETPOINTS
OCSP
Occupied Cool Setpoint
UCSP
Unoccupied Cool Setpoint
OHSP
Occupied Heat Setpoint
UHSP
Unoccupied Heat Setpoint
GAP
Heat-Cool Setpoint Gap
STO.R
SPT Offset Range (+/–)
RH.SP
Space RH Setpoint
RH.DB
Space RH Deadband
RH.HB
Reheat Heat SP Deadband
CA.LO
Circuit A Lockout Temp
CB.LO
CB LO
Circuit B Lockout Temp
Circuit B Lockout Temp
CC.LO
Circuit C Lockout Temp
HT.LO
Heating Lockout Temp
EH.LO
Econo Cool Hi Temp Limit
EL.LO
Econo Cool Lo Temp Limit
FC.LO
Free Cool Low Temp Limit
LCSP
Low Cool SAT Setpoint
HCSP
High Cool SAT Setpoint
SAT.U
Minimum SAT Upper Level
SAT.L
Minimum SAT Lower Level
ITEM
EXPANSION
INPUTS
STAT
Thermostat Inputs
Y1
Thermostat Y1 Input
Y2
Thermostat Y2 Input
W1
Thermostat W1 Input
W2
Thermostat W2 Input
G
Thermostat G Input
GEN.I
General Inputs
FIL.S
Filter Status Switch
FAN.S
Fan Status Switch
FDWN
Fire Shutdown Switch
ENTH
Outdoor Enthalpy Switch
RM.OC
Remote Occupancy Switch
HUM
Space Humidity Switch
CS.IN
Current Sensor Inputs
CS.A1
Compressor A1 Feedback
CS.A2
Compressor A2 Feedback
CS.B1
Compressor B1 Feedback
CS.C1
Compressor C1 Feedback
AIR.Q
Air Quality Inputs
IAQ.S
IAQ Level (Switch)
IAQ
IAQ Level (Sensor)
OAQ
OAQ Level (Sensor)
SP .RH
Space Humidity Sensor
ITEM
EXPANSION
OUTPUTS
FANS
Fan Outputs
IDF
Indoor Fan Relay
OFC.1
Outdoor Fan 1 Relay
OFC.2
Outdoor Fan 2 Relay
OFC.3
Outdoor Fan 3 Relay
COOL
Cool Outputs
CMP .A
Circuit A Compressors
CMP .B
Circuit B Compressors
CMP .C
Circuit C Compressors
CCH
Crankcase Heat Relay
CRC
Cool−>Reheat1 Control
RH2.A
Reheat2 Valve A
RH2.B
Reheat2 Valve BC
HEAT
Heat Outputs
HT.1
Heat Stage 1 Relay
HT.2
Heat Stage 2 Relay
ECON
Economizer Outputs
EC.CP
Econo Commanded Position
EC.AP
Econo Actual Position
PE.1
Power Exhaust 1 Relay
PE.2
Power Exhaust 2 Relay
ALRM
Alarm Relay
MODE — SET POINTS
VALUES
UNITS
NAME
55 to 80
dF
75 to 95
dF
55 to 80
dF
40 to 80
dF
2 to 10
dF
1 to 5
^F
30 to 95
%
2 to 20
%
–5 to 5
^F
0 to 100
dF
0 to 100
0 to 100
dF
dF
0 to 100
dF
40 to 125
dF
40 to 100
dF
–30 to 50
dF
–35 to 70
dF
55 to 75
dF
50 to 70
dF
35 to 65
dF
35 to 65
dF
RANGE
On/Off
On/Off
On/Off
On/Off
On/Off
Dirty/Clean
On/Off
On/Off
High/Low
On/Off
High/Low
On/Off
On/Off
On/Off
On/Off
High/Low
xxxx
xxxx
xxx.x
MODE — OUTPUTS
RANGE
On/Off
On/Off
On/Off
On/Off
On/Off
On/Off
On/Off
On/Off
On/Off
On/Off
On/Off
On/Off
On/Off
0 to 100
0 to 100
On/Off
On/Off
On/Off
DEFAULT
78
85
68
60
5
5
50
5
2
0
0: no Humidi-Mizer
40: Humidi-Mizer (03-16)
0
75
65
0
50
55 (03-07)
65 (08-16)
55
60
35 (03-07)
45 (08-14)
50 (16)
MODE — INPUTS
CCN TABLE/
UNITS
SUB-TABLE
STATUS DISPLAY
STATUS DISPLAY
UINPUT
UINPUT
ppm
ppm
%
CCN TABLE/
UNITS
SUB-TABLE
STATUS DISPLAY
STATUS DISPLAY
UOUTPUT
UOUTPUT
%
%
125
CCN TABLE/
SUB-TABLE
SETPOINT CONFIGURATION
SETPOINT CONFIGURATION
SET_PNT
SET PNT
CCN
POINT
Y1
Y2
W1
W2
G
FILTSTAT
FAN_STAT
FIREDOWN
ENTHALPY
REM_OCC
HUM_STAT
CS_A1
CS_A2
CS_B1
CS_C1
IAQIN
IAQ
OAQ
SPRH
CCN
POINT
IDF
OFC_1
OFC_2
OFC_3
COMP_A
COMP_B
COMP_C
CCH
CRC
RH2_A
RH2_B
HEAT_1
HEAT_2
ECONOCMD
ECONOPOS
PE_1
PE_2
ALMOUT
CCN
NAME
OCSP
UCSP
OHSP
UHSP
HCSP_GAP
SPTO_RNG
SPRH_SP
SPRH_DB
RH_HSPDB
OATLCMPA
OATLCMPB
OATLCMPC
OATLHEAT
OATLECLH
OATLECLL
OATLUEFC
LCSASP
HCSASP
SATMIN_H
SATMIN_L
WRITE
STATUS
Forcible
Forcible
Forcible
Forcible
Forcible
Forcible
Forcible
Forcible
Forcible
Forcible
Forcible
Forcible
Forcible
WRITE
STATUS
Forcible
Forcible
Forcible
Forcible