APPENDIX A — LOCAL DISPLAY AND CCN TABLES (CONT)
ITEM
EXPANSION
CONFIGURATION (cont)
COOL (cont)
CIR.B
Circuit B
CS.B1
B1 Current Sensing
B1.FN
B Circuit Level 1 Fans
B2.FN
B Circuit Level 2 Fans
B3.FN
B Circuit Level 3 Fans
CIR.C
Circuit C
CS.C1
C1 Current Sensing
C1.FN
C Circuit Level 1 Fans
C2.FN
C Circuit Level 2 Fans
C3.FN
C Circuit Level 3 Fans
SST
Low Suction Control
SST.O
Suction OK Temperature
SST.1
Low Suction — Level 1
SST.2
Low Suction — Level 2
SST.3
Low Suction — Level 3
OFC
Outdoor Fan Control
OFC.3
OFC3 Enable. CCH Disable
0.MXP
Fan Lev0 Max Pressure
1.MXP
Fan Lev1 Max Pressure
2.MNP
Fan Lev2 Min Pressure
2.ON
Fan Lev2 On Temperature
2.OFF
Fan Lev2 Off Temperature
2.MXP
Fan Lev2 Max Pressure
3.MNP
Fan Lev3 Min Pressure
3.ON
Fan Lev3 on Temperature
3.OFF
Fan Lev3 Off Temperature
LEGEND
FIOP --- --- Factory ---Installed Option
MODE — CONFIGURATION (cont)
RANGE
UNITS
Enable/Disable
Disable (03-07)
Enable (08-16)
0 to 7
No Humidi-MiZer FIOP
0 (03-07)
3 (08-16)
Humidi-MiZer FIOP
0
0 to 7
No Humidi-MiZer FIOP
0 (03-07)
3 (08-16)
Humidi-MiZer FIOP
0 (03-14)
1 (16)
0 to 7
No Humidi-MiZer FIOP
0 (03-07)
3 (08-16)
Humidi-MiZer FIOP
0 (03-14)
1 (16)
Enable/Disable
Disable (03-14)
Enable (16)
0 to 7
No Humidi-MiZer FIOP
0 (03-14)
1 (16)
Humidi-MiZer FIOP
0
0 to 7
No Humidi-MiZer FIOP
0 (03-14)
3 (16)
Humidi-MiZer FIOP
0 (03-14)
1 (16)
0 to 7
No Humidi-MiZer FIOP
0 (03-14)
3 (16)
Humidi-MiZer FIOP
0 (03-14)
1 (16)
10 to 50
dF
18
10 to 50
dF
20
5 to 50
dF
15
0 to 50
dF
10
Yes/No
No (03-16)
Yes (20-28)
100 to 500
psig
200
100 to 500
psig
400 (03-16)
450 (20-28)
100 to 500
psig
150 (03-16)
200 (20-28)
0 to 100
F
no Humidi-MiZer FIOP:
55 (03-16)
55 (20)
45 (24-28)
Humidi-MiZer FIOP:
68 (20)
61 (24)
61 (28)
0 to 100
F
no Humidi-MiZer FIOP:
45 (03-16)
50 (20)
40 (24-28)
Humidi-MiZer FIOP:
57 (20)
57 (24)
57 (28)
100 to 500
psig
400
100 to 500
psig
250
0 to 100
F
no Humidi-MiZer FIOP:
65
Humidi-MiZer FIOP:
88 (20)
68 (24)
68 (28)
0 to 100
F
no Humidi-MiZer FIOP:
55
Humidi-MiZer FIOP:
78 (20)
62 (24)
62 (28)
127
DEFAULT
CCN TABLE/ SUB-TABLE
LOW SUCTION CONTROL
OUTDOOR FAN CONTROL
PAGE
CCN POINT
NO.
B1_SENSE
80
CIR_B_1
CIR_B_2
CIR_B_3
C1_SENSE
80
CIR_C_1
CIR_C_2
CIR_C_3
SSTOK
SSTLEV1
81
SSTLEV2
81
SSTLEV3
81
64
OFC3_CTL
81
LEV0MAXP
LEV1MAXP
LEV2MNP
LEV2ON
LEV2OFF
LEV2MAXP
LEV3MINP
LEV3ON
LEV3OFF

Hide quick links: