AIRFLOW
AIRFLOW
0.2
(Cfm)
(Cfm)
Rpm
1200
456
1300
477
1400
500
1500
524
1600
550
1700
576
1800
604
1900
633
2000
662
AIRFLOW
AIRFLOW
1.2
(Cfm)
(Cfm)
Rpm
1200
929
1300
934
1400
941
1500
951
1600
963
1700
976
1800
991
1900
1008
2000
1026
LEGEND
Bhp --- Brake Horsepower
High Range Motor/Drive Required
AIRFLOW
AIRFLOW
0.2
(Cfm)
(Cfm)
Rpm
1500
521
1600
546
1700
572
1800
599
1900
627
2000
655
2100
684
2200
714
2300
744
2400
775
2500
806
AIRFLOW
AIRFLOW
1.2
(Cfm)
(Cfm)
Rpm
1500
949
1600
961
1700
974
1800
988
1900
1004
2000
1022
2100
1040
2200
1060
2300
1081
2400
1102
2500
1124
LEGEND
Bhp --- Brake Horsepower
Table 37—Fan Performance — 48PGF05 Horizontal Units
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
0.4
Bhp
Rpm
Bhp
0.13
574
0.20
0.16
591
0.23
0.18
610
0.27
0.22
630
0.31
0.26
652
0.35
0.30
675
0.40
0.35
699
0.46
0.41
724
0.52
0.47
750
0.59
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
1.4
Bhp
Rpm
Bhp
0.56
1003
0.66
0.60
1006
0.71
0.65
1012
0.76
0.71
1020
0.82
0.77
1029
0.89
0.84
1041
0.96
0.91
1054
1.04
0.99
1070
1.12
1.08
1086
1.21
Table 38—Fan Performance — 48PGD06 Horizontal Units
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
0.4
Bhp
Rpm
Bhp
0.22
628
0.31
0.25
649
0.35
0.30
671
0.40
0.35
695
0.45
0.40
719
0.51
0.46
745
0.58
0.53
771
0.66
0.61
797
0.74
0.69
824
0.83
0.78
852
0.92
0.88
880
1.03
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
1.4
Bhp
Rpm
Bhp
0.70
1018
0.82
0.77
1027
0.88
0.83
1039
0.95
0.91
1052
1.03
0.99
1066
1.11
1.07
1082
1.20
1.17
1099
1.30
1.27
1117
1.41
1.38
1136
1.52
1.50
1156
1.65
1.62
1177
1.78
0.6
0.8
Rpm
Bhp
Rpm
675
0.28
766
688
0.32
776
703
0.36
788
720
0.40
802
739
0.45
819
759
0.50
836
781
0.57
856
804
0.63
876
828
0.71
898
1.6
1.8
Rpm
Bhp
Rpm
1073
0.76
1139
1075
0.82
1140
1079
0.87
1143
1085
0.94
1148
1093
1.01
1155
1103
1.08
1163
1115
1.16
1174
1129
1.25
1186
1144
1.35
1199
NOTES:
1. Motor drive range is 596 to 910 rpm for low range motor/drive, 828 to 1173 rpm for
high range motor/drive. All other rpms require a field-supplied drive.
2. Maximum continuous bhp is 0.85 for low range motor/drive and 1.60 (single phase)
and 2.40 (3 phase) for high range motor/drive.
3. See General Fan Performance Notes.
0.6
0.8
Rpm
Bhp
Rpm
718
0.40
800
737
0.45
816
757
0.50
834
777
0.56
852
799
0.63
872
822
0.70
893
846
0.78
915
871
0.87
938
896
0.96
961
922
1.06
985
948
1.18
1010
1.6
1.8
Rpm
Bhp
Rpm
1083
0.93
1146
1091
1.00
1153
1101
1.08
1161
1112
1.16
1171
1125
1.25
1182
1139
1.34
1195
1155
1.44
1209
1172
1.55
1225
1190
1.67
1242
1209
1.80
1259
1228
1.94
1278
NOTES:
1. Motor drive range is 690 to 978 rpm for low range motor/drive and 929 to 1261 rpm
for high range motor/drive. All other rpms require a field-supplied drive.
2. Maximum continuous bhp is 0.85 (single phase) and 2.40 (3 phase) for low range
motor/drive and 1.60 (single phase) and 2.40 (3 phase) for high range motor/drive.
3. See General Fan Performance Notes.
26
1.0
Bhp
Rpm
Bhp
0.37
850
0.46
0.41
857
0.50
0.45
867
0.55
0.50
879
0.60
0.55
893
0.66
0.61
908
0.72
0.68
925
0.79
0.75
944
0.87
0.83
964
0.95
2.0
Bhp
Rpm
Bhp
0.87
1202
0.98
0.93
1202
1.05
0.99
1204
1.11
1.06
1208
1.18
1.13
1214
1.26
1.21
1221
1.34
1.30
1230
1.43
1.39
1241
1.53
1253
1.63
1.49
1.0
Bhp
Rpm
Bhp
0.49
877
0.60
0.55
890
0.65
0.61
906
0.72
0.67
922
0.79
0.74
940
0.86
0.82
959
0.94
0.91
979
1.03
1.00
1001
1.13
1.10
1022
1.24
1.21
1045
1.35
1.32
1069
1.47
2.0
Bhp
Rpm
Bhp
1.05
1207
1.18
1.13
1212
1.26
1.21
1219
1.34
1.29
1227
1.43
1.38
1238
1.52
1.48
1249
1.62
1.59
1262
1.73
1.70
1277
1.85
1.82
1292
1.98
1.96
1309
2.12
2.10
1326
2.26

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

50pg03-16

Table of Contents