Carrier 48PG03-16 Controls, Start-Up, Operation, Service And Troubleshooting Instructions page 138

Single package small rooftop units with comfort link controls and puron (r---410a) refrigerant
Hide thumbs Also See for 48PG03-16:
Table of Contents

Advertisement

ITEM
CONFIGURATION (cont)
ECON (cont)
FC.TM
Free Cool PreOcc Time
FC.LO
Free Cool Low Temp Limit
PE.EN
Power Exhaust Installed
PE.1
PE Stage1 Econo
Position
PE.2
PE Stage2 Econo
Position
EN.SW
Enthalpy Switch
E.TRV
Economizer Travel Time
E.MXB
Bottom Stage Max Econo
E.MXM
Middle Stage Max Econo
E.MXT
Top Stage Max Econo
E.DBD
Economizer PID
Deadband
EC.P
Economizer PID — kP
EC.I
Economizer PID — kI
EC.D
Economizer PID — kD
EC.DT
Economizer PID — rate
AIR.Q
Air Quality Configuration
IA.CF
IAQ Analog Input Config
IA.FN
IAQ Analog Fan Config
II.CF
IAQ Switch Input Config
II.FN
IAQ Switch Fan Config
AQ.MN
Econo Min IAQ Position
EC.MN
Econo Minimum Position
OVR.P
IAQ Override Position
OA.CF
OAQ Analog Input Cfg
OAQ.L
OAQ Lockout Limit
AQD.L
AQ Differential Low
AQD.H
AQ Differential High
DF.ON
Fan On AQ Differential
DF.OF
Fan Off AQ Differential
I.4M
IAQ Sensor Value at 4mA
I.20M
IAQ Sensor Value at 20mA
O.4M
OAQ Sensor Value at 4mA
O.20M
OAQ Sensor Value at
20mA
H.4M
RH Sensor Value at 4mA
H.20M
RH Sensor Value at 20mA
Alarm Relay
ALM.O
Configuration
A.SPC
SPT/SPRH Sensor
Failure
A.SRT
SAT/RAT Sensor Failure
A.OAT
OAT Thermistor Failure
A.CS
Current Sensor Failure
A.CMP
Compressor Failure
A.CKT
Refrigerant Circuit Failure
A.SSP
SSP Transducer Failure
A.SCT
SCT Thermistor Failure
A.FAN
Indoor Fan Failure
A.FIL
Dirty Filter
A.TST
Thermostat Failure
A.ECO
Economizer Failure
MODE — CONFIGURATION (cont)
EXPANSION
RANGE
1 to 9999 min
0 to 70 dF
Yes/No
10 to 100 %
10 to 100 %
0=No Switch
1=Normally Open
2=Normally Closed
5 to 300 sec
0 to 100 %
1 to 100 %
0 to 100 %
0 to 25 %
0.0 to 99.9 sec
0.0 to 99.9 sec
0.0 to 99.9 sec
10.0 to 180.0 sec
0=No IAQ
1=Demand Ventilation
2=Econ Position Override
3=Econ Min Position Con-
trol
0=Never
1=Only While Occupied
2=Always
0=No IAQ
1=DCV Normally Open
2=DCV Normally Closed
3=Override Normally
Open
4=Override Normally
Closed
0=Never
1=Only While Occupied
2=Always
0 to 100
0 to 100
0 to 100
0=No OAQ
1=Demand Ventilation
2=Outdoor Air Lockout
0 to 5000
0 to 5000
0 to 5000
0 to 5000
0 to 5000
0 to 5000
0 to 5000
0 to 5000
0 to 5000
0 to 50 %
60 to 100 %
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
DEFAULT
120
50
No: no FIOP
Yes: FIOP
40
75
0: no FIOP
1: FIOP
150
50
35
25
3
2.5
0.1
1
15
0: no FIOP
1: FIOP
0
0
0
10
30
100
0
600
100
700
600
200
0
2000
0
2000
0
100
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
138