ITEM
CONFIGURATION (cont)
OFC (cont)
3.OFF
Fan Lev3 Off Temperature
HMZR
Humidimizer Config
REHT
Humidimizer Equipped
R.DEC
Reheat2 Stage Decr. Time
R.INC
Reheat2 Stage Incr. Time
RH.FN
Reheat Fan Control
RF.LV
Reheat2 ODF Fan On Lev-
el
RF.ON
Reheat2 ODF Fan On
Temp
RF.OF
Reheat2 ODF Fan Off
Temp
RA.LO
Reheat2 OAT Limit A
RA.LP
Reheat2 SSP Lo Limit A
RA.HP
Reheat2 SSP Hi Limit A
RB.LO
Reheat2 OAT Limit B, C
RB.LP
Reheat2 SSP Lo
Limit B, C
RB.HP
Reheat2 SSP Hi
Limit B, C
HEAT
Heating Configuration
HT.TY
Type of Heat Installed
N.HTR
Number of Heat Stages
MRT.H
Heat Minimum On Time
MOT.H
Heat Minimum Off Time
H.DEC
Heat Stage Decrease Rate
H.INC
Heat Stage Increase Rate
FOD.E
Fan-off Delay, Elect Heat
FOD.G
Fan-off Delay, Gas Heat
HT.LO
Heating Lockout Temp
SAT.H
SAT Heat Mode Sensing
SPT
Space Temperature
Sensor
HT.PD
SPT Heat Demand (+)
Level
HT.ND
SPT Heat Demand (–) Lev-
el
H.LAG
Heat Thermal Lag Factor
ECON
Economizer Configuration
EC.EN
Economizer Installed
E.CTL
Economizer Control Type
EC.MN
Econo Minimum Position
EC.MX
Econo Cool Max Position
EH.LO
Econo Cool Hi Temp Limit
EL.LO
Econo Cool Lo Temp Limit
UEFC
Unoccupied Free Cooling
LEGEND
FIOP --- --- Factory ---Installed Option
MODE — CONFIGURATION (cont)
EXPANSION
RANGE
0 to 100 F
Yes/No
0 to 999 secs
0 to 999 secs
Yes/No
0 to 3
0 to 100 F
0 to 100 F
20 to 70 F
50 to 100 psig
50 to 100 psig
20 to 70 F
50 to 100 psig
50 to 100 psig
0 = No Heat
1 = Gas
2 = Electric
1 to 2
60 to 999 sec
60 to 999 sec
120 to 999 sec
120 to 999 sec
10 to 600 sec
45 to 600 sec
40 to 125 dF
Enable/Disable
0.5 to 5 ^F
–5 to –0.5 ^F
0 to 5 min
Yes/No
1=Digital, Position
Feedback
2=Digital, Command
Feedback
3=Analog Control
0 to 100 %
0 to 100 %
40 to 100 dF
–30 to 50 dF
0=Disabled
1=Entire Unoccupied
Period
2=PreOccupancy Time
DEFAULT
no Humidi-MiZer FIOP:
55
Humidi-MiZer FIOP:
78 (20)
62 (24)
62 (28)
No: no Humidi-MiZer FIOP
Yes: Humidi-MiZer FIOP
60
300
No (03-14)
Yes (16-28)
2
75 (16)
93 (20)
93 (24)
85 (28)
70 (16)
83 (20)
88 (24)
80 (28)
40
80 (03-16)
80 (20-28)
90 (03-16)
90 (20-28)
50 (08-14)
50 (16, 20-28)
80 (03-16)
80 (20-28)
90 (03-16)
90 (20-28)
0 (50 series with no
electric heat)
1 (48 series)
2 (50 series with electric
heat)
1 (48 series 1-phase,
50 series <15kW)
2 (48 series 3-phase,
50 series >=15kW)
120
120
300
450
30
45
75
Disable
1
–1
1
No: no FIOP
Yes: FIOP
1
30
100
65
0
2
137