APPENDIX A — LOCAL DISPLAY AND CCN TABLES (CONT)
ITEM
EXPANSION
CONFIGURATION (cont)
HMZR
Humidimizer Config
REHT
Humidimizer Equipped
R.DEC
Reheat2 Stage Decr. Time
R.INC
Reheat2 Stage Incr. Time
RH.FN
Reheat Fan Control
RF.LV
Reheat2 ODF Fan On Level
RF.ON
Reheat2 ODF Fan On Temp
RF.OF
Reheat2 ODF Fan Off Temp
RA.LO
Reheat2 OAT Limit A
RA.LP
Reheat2 SSP Lo Limit A
RA.HP
Reheat2 SSP Hi Limit A
RB.LO
Reheat2 OAT Limit B, C
RB.LP
Reheat2 SSP Lo Limit B, C
RB.HP
Reheat2 SSP Hi Limit B, C
HEAT
Heating Configuration
HT.TY
Type of Heat Installed
N.HTR
Number of Heat Stages
MRT.H
Heat Minimum On Time
MOT.H
Heat Minimum Off Time
H.DEC
Heat Stage Decrease Rate
H.INC
Heat Stage Increase Rate
FOD.E
Fan-off Delay, Elect Heat
FOD.G
Fan-off Delay, Gas Heat
HT.LO
Heating Lockout Temp
SAT.H
SAT Heat Mode Sensing
SPT
Space Temperature Sensor
HT.PD
SPT Heat Demand (+) Level
HT.ND
SPT Heat Demand (–) Level
H.LAG
Heat Thermal Lag Factor
ECON
Economizer Configuration
EC.EN
Economizer Installed
E.CTL
Economizer Control Type
EC.MN
Econo Minimum Position
EC.MX
Econo Cool Max Position
EH.LO
Econo Cool Hi Temp Limit
EL.LO
Econo Cool Lo Temp Limit
UEFC
Unoccupied Free Cooling
FC.TM
Free Cool PreOcc Time
FC.LO
Free Cool Low Temp Limit
PE.EN
Power Exhaust Installed
PE.1
PE Stage1 Econo Position
PE.2
PE Stage2 Econo Position
EN.SW
Enthalpy Switch
E.TRV
Economizer Travel Time
E.MXB
Bottom Stage Max Econo
E.MXM
Middle Stage Max Econo
E.MXT
Top Stage Max Econo
E.DBD
Economizer PID Deadband
EC.P
Economizer PID — kP
EC.I
Economizer PID — kI
EC.D
Economizer PID — kD
EC.DT
Economizer PID — rate
LEGEND
FIOP --- --- Factory ---Installed Option
MODE — CONFIGURATION (cont)
RANGE
UNITS
Yes/No
0 to 999
secs
0 to 999
secs
Yes/No
0 to 3
0 to 100
F
0 to 100
F
20 to 70
F
50 to 100
psig
50 to 100
psig
20 to 70
F
50 to 100
psig
50 to 100
psig
0 = No Heat
1 = Gas
2 = Electric
1 to 2
60 to 999
sec
60 to 999
sec
120 to 999
sec
120 to 999
sec
10 to 600
sec
45 to 600
sec
40 to 125
dF
Enable/Disable
0.5 to 5
^F
–5 to –0.5
^F
0 to 5
min
Yes/No
1=Digital, Position Feedback
2=Digital, Command Feed-
back
3=Analog Control
0 to 100
%
0 to 100
%
40 to 100
dF
–30 to 50
dF
0=Disabled
1=Entire Unoccupied Period
2=PreOccupancy Time
1 to 9999
min
0 to 70
dF
Yes/No
10 to 100
%
10 to 100
%
0=No Switch
1=Normally Open
2=Normally Closed
5 to 300
sec
0 to 100
%
1 to 100
%
0 to 100
%
0 to 25
%
0.0 to 99.9
sec
0.0 to 99.9
sec
0.0 to 99.9
sec
10.0 to 180.0
sec
CCN
DEFAULT
TABLE/SUB-TABLE
No: no Humidi-MiZer
FIOP
Yes: Humidi-MiZer FIOP
60
300
No (03-14)
Yes (16-28)
2
75 (16)
93 (20)
93 (24)
85 (28)
70 (16)
HMZR CFG
83 (20)
88 (24)
80 (28)
40
80 (03-16)
80 (20-28)
90 (03-16)
90 (20-28)
50 (08-14)
50 (16, 20-28)
80 (08-16)
80 (20-28)
90 (08-16)
90 (20-28)
0 (50 series with no
electric heat)
1 (48 series)
2 (50 series with electric
heat)
1 (48 series 1-phase,
50 series <15kW)
2 (48 series 3-phase,
50 series >=15kW)
120
120
HEAT CFG
HEAT_CFG
300
450
30
45
75
Disable
1
–1
1
No: no FIOP
Yes: FIOP
1
30
100
65
0
2
120
50
ECON_CFG
No: no FIOP
Yes: FIOP
40
75
0: no FIOP
1: FIOP
150
50
35
25
3
2.5
0.1
1
15
128
PAGE
CCN POINT
NO.
64, 69
REHEAT
70,81
RSTAGDEC
70
RSTAGINC
70
RHFANCTL
70, 81
RHFANLEV
70
RHFANON
70
RHFANOFF
70
OATLRH_A
70
RHSSPL_ A
70
RHSSPH_A
70
OATLRH_B
70
RHSSPL_B
70
RHSSPH_B
70
HEATTYPE
64, 66,
111
NUM_HEAT
66, 111
HMIN_ON
64, 66
HMIN_OFF
64, 66
HSTAGDEC
64, 66
HSTAGINC
64, 66
ELEC_FOD
66
GAS_FOD
64
OATLHEAT
64, 66
SAT_HEAT
66
HDEM_POS
HDEM_NEG
HEAT_LAG
ECONO
66
ECON_CTL
55, 67, 94
ECONOMIN
66
ECONOMAX
66
OATLECLH
OATLECLL
UEFC_CFG
67
UEFCTIME
67
OATLUEFC
67
PE_ENABL
67, 111
PE1_POS
67
PE2_POS
67
ENTHLCFG
59, 111
ECONOTRV
ECONMAXB
ECONMAXM
ECONMAXT
ECONBAND
ECONO_P
ECONO_I
ECONO_D
ECONO_DT