Paired outputs
Defines whether the outputs are controlled individually or whether they are controlled as paired
outputs. If the outputs are defined to act using paired operation writing the value 0 to output N
causes output N to become active and output N+1 to become inactive. Writing value 1 to output N
causes output N to become inactive and output N+1 to become active. In paired mode only the
even (0, 2, 4, ...) outputs can be addressed.
IO extension paired outputs
Type
Units
Value range
Note
Forced output function
Defines the forced operation of outputs executed regardless of the actual command data. E.g. if
the forced function is "short pulse" and command data requires "persistent value" short pulse is
generated.
IO extension forced output function
Type
Units
Value range
Note
Send input status cyclic
Defines whether the input pin status information is sent cyclically when the IEC-104 connection is
active.
IO extension cyclic input status reporting
Type
Units
Value range
Note
Arctic IEC-104 Gateway
Boolean
N/A
No, Yes
Output function
N/A
None, Short pulse, Long pulse, Persistent
Boolean
N/A
No, Yes
In any case the status of input pins can be requested by
polling.
47
User's Manual
Viola Systems Ltd.