5.0
Site Requirements - Page 13
5.5 Ventilation of Compartments
1. Where the appliance is installed in a cupboard or
compartment, no air vents are required.
NOTE: The ventilation label on the front of the outer
case MUST NOT BE REMOVED when the appliance is
installed in a compartment or cupboard.
2. B.S. 5440 Part 2 Clause 4.2 refers to room sealed
appliances installed in compartments. This appliance will run
sufficiently cool without ventilation.
5.6 Gas Supply
1. The gas installation should be in accordance with BS
6891.
2. The connection of the appliance is a 22mm copper tail on
the tap rail (Fig. 12).
3. The pipework should be sized to account for the distance
of the appliance from the meter, the pipe routing and
maximum input of the appliance.
5.7 Electrical Supply
External wiring must be correctly earthed, polarized and in
accordance with CURRENT I.E.E. WIRING REGULATIONS.
The mains supply is 230V ~ 50Hz fused at 5A.
NOTE: The method of connection to the electricity
supply must facilitate complete electrical isolation of the
appliance.
Connection may be made via a fused double-pole isolator
with a contact separation of a least 3mm in all poles and
serving the appliance and system controls only.