7.0
Commissioning the Appliance - Page 33
7.1 Commissioning the Appliance (Cont)
1. From the table opposite check that the main burner
pressure is correct after the appliance has been running for
10 minutes.
2. Check for gas soundness, with main burner alight, using
leak detection fluid.
3. If necessary, adjustment to main burner pressure can be
made by altering the regulator as shown (Fig. 84).
4. To alter the burner pressure, turn the adjustment screw in
either direction until the required pressure is obtained (Fig.
84).
5. Turn the boiler thermostat to the OFF position marked 0.
Remove the pressure gauge and screw home the pressure
test point screw. Turn the boiler thermostat knob to the
required setting (Fig. 84).
6. The boiler and system should be run and then flushed
and treated in accordance with BS 7593:1992 and the
flushing agent / inhibitor manufacturers instructions.
Pressurise the system to 1.0 bar then close and disconnect
the filling loop.
7. When all the air has been removed from the water circuit,
the pump and radiators should be balanced to achieve the
design temperature drop across the system.
8. Make a final check for gas soundness and set any timer
control, room thermostats etc. to the customers specific
requirements.
9. The boiler is protected by an integral frost-stat, but if the
boiler is not to be used for a long period of time, the system
should be drained.
NOTE: The frost thermostat operates even if the boiler
thermostat is in the OFF position and it is necessary
therefore, if the system is drained, for the external
electrical and gas supplies to be isolated.
It is recommended that a label be affixed to the
appliance to draw attention to the fact that the system
has been drained.
WARNING - If the system is filled with very cold water
and the boiler lit, the action of the frost protection
thermostat will prevent the boiler from shutting down
o
before the water temperature reaches 10
C.